Technical Product Information 

March 2008 

AP 257/41 Wind sensor 

5WG1 257-3AB41 

 

Siemens AG 

AP 257/41, 4 pages 

Technical Manual 

Industry Sector, Building Technologies 

 

 

Electrical Installation Technology 

©

 Siemens AG 2008 

Update: http://www.siemens.com/gamma 

P.O.Box 10 09 53, D-93009 Regensburg 

Subject to change without prior notice 

 

 

2.13.5.1/1 

Product and Applications Description 

 

 

 

The AP 257/41 wind sensor contains the sensor and the 
electronic systems for wind data analysis and bus inter-
facing in one compact enclosure.  
The wind speed can be sent to the bus in the EIS5 format 
and monitored respectively for up to 3 limit values. Limit 
values can be selected as parameters or as communica-
tion objects. Additionally the maximum wind speed can 
be recorded, stored, requested and reset.  
In addition, 8 AND-gates and 8 OR-gates are available 
with 4 inputs each for logical combinations. If the wind 
speed is measured at different locations / facades the 
logic gates may be used e.g. for the logical combination 
of the wind alarms from several wind sensors to an over-
all alarm. 
The voltage supply of the electronics takes place via AC 
20 V or DC 24 V safety extra-low voltage (SELV). For the 
transmission of this voltage, the white / yellow twisted 
pair of the bus cable can be used.

 

  

Application Program 

 

The AP 257/41 wind sensor has to be used together with 
the application program “0701 CO wind sensor 910101” 
which can be configured and loaded with the Engineer-
ing Tool Software (ETS) from version ETS2 V1.3. But it is 
recommended to use the engineering tool software 
ETS3, since it presents a graphically optimal display of 
the setting menus of the wind sensor. 

 

Installation Instructions 

 

If the wind sensor should be damaged, it must not be 
commissioned.  

 

V

 

WARNING 

 

The device must be mounted and commissioned by an 
authorised electrician. 

 

For planning and construction of electric installations, 
the relevant guidelines, regulations and standards of 
the respective country are to be considered. 

Technical Specifications 

 

Sensors

 

 

Wind sensor:  
- Measuring range: 0 ... 70 m/s 
- Resolution: < 10% of the measuring range 

 

Voltage supply  

 

Bus voltage: via the bus line 

 

Bus current: 9 mA  

 

Sensor electronics: AC 20 V +10% 50/60 Hz or DC 24 V 
+ 10% max. 110 mA, residual ripple < 10%, max. per-
missible cable length 100 m 

 

Power consumption: at AC 20 V: max. 2.2 VA; 
at DC 24 V: max. 2.64W 

 
Connections 

 

Voltage supply: plug terminals for solid conductors or 
finely stranded conductors 0.5 ... 1.5mm²  

 

Bus connection: screw-less bus terminal, single-core 
0.6...0.8 mm 

 single-core, insulation strip length 5 mm.

 

 

Mechanical data  

 

Housing: plastic 

 

Dimensions: approx. 118mm x 96mm x 77mm (LxWxH) 

 

Weight: approx. 145 g  

 

Mounting: Mast or wall mounting  

 

Electric safety 

 

Protection type (according to EN 60529): IP44 

 

Bus: safety extra low voltage (SELV) DC 24 V 

 

Device complies with EN 50090-2-2  

 
EMC requirements 

 

complies with EN 50090-2-2 

 

Environmental conditions 

 

Ambient temperature during operation: - 30 ... + 50 °C 

 

 Storage temperature: - 20 ... + 70 °C 

 

rel. humidity (not condensing): 5 ... 93 % 

 

Markings 

KNX  

EIB

 

 

CE mark 

complies with the EMC regulations (residential and func-
tional buildings), and low voltage regulations 

 

Содержание AP 257/41

Страница 1: ...ineer ing Tool Software ETS from version ETS2 V1 3 But it is recommended to use the engineering tool software ETS3 since it presents a graphically optimal display of the setting menus of the wind sensor Installation Instructions If the wind sensor should be damaged it must not be commissioned V WARNING The device must be mounted and commissioned by an authorised electrician For planning and constr...

Страница 2: ...7 Commissioning LED for display of normal mode addressing mode off on Mounting and wiring Location Select a position on the building where wind can be recorded by the sensor without impairment There must be at least 60 cm free space under the wind sensor to allow for correct wind measurements and to prevent the sensor being snowed in case of snow The wind sensor must be mounted on a mast or a vert...

Страница 3: ...airs for the voltage supply and the bus to the provided terminals while taking polarity into account see fig 2 Fastening the wind sensor Close the enclosure by putting the lid over the lower part The lid must snap into place on the left and the right with a clear click Check that the lid and lower part are properly snapped into place Fig 11 shows the cor rectly closed wind sensor from below Figure...

Страница 4: ... The wind sensor should be regularly checked twice per year for soiling and cleaned if necessary In case of strong pollution the wind sensor may cease to function During maintenance and cleaning the wind sensor should always be separated from the bus and the supply voltage for safety purposes General Notes Any faulty devices should be returned to the local Siemens office If you have further questi...