Line plug-in modules
63
Building Technologies
008725_h_en_--
Fire Safety & Security Products
06.2011
26 Line
plug-in
modules
There are different line plug-in modules for the various detector systems:
–
E3M071 for interactive detectors
–
E3M171 for interactive 'Ex' detectors
–
E3M120 for CBA8000/TS9000 detectors
–
E3M111 for AnalogPLUS detectors
–
E3M060 for MS9i detectors
–
E3M080 for collective detectors (limit value detectors)
–
E3M141 for Sinteso
TM
devices
24V
max
.500mA
I-Bus
E3M071
E3X10.
ST10
24V
max.
500mA
E3M060
ST10
E3M080
ST10
24V
E3M111
1
2......... 8
E3M171
ST10
ST10
1........4
E3M120
E3M141
MIMIC DISPLAY
1...... ..4
1........2
max
.500mA
ST10/MIMIC DISPLAY
= plug for special application (E3G110) –> see page 88
Detector
system
AlgoRex
Interactive
AlgoRex
Interactive Ex
CBA8000
TS9000
AlgoRex
AnalogPLUS
MS9i
MS9i-PLUS
MS716i
AlgoRex
Collective
MS6/7/9
(MS6: Detectors
without
light bulbs only
as AI)
Sinteso
TM
addressed
Number of
lines
1
1 4 4 1 8
2
No. of
addresses
1 x 128
1 x 32
4 x 119
4 x 128
1 x 50
8
2 x 126
Loop line
–
–
Stub line
–
Short
circuit
isolator
In every HFM and
I/O module.
Detectors both with
and without
–
In every
device
In every
device
In every
device
–
In every device
Special
features
Any number of
T-branches
Sep. 24 V feed
output for
I/O modules
Response indi-
cator output
on detector
can be pro-
grammed
Any number of
T-branches
Response
indicator out-
put
on detector
can be pro-
grammed
Sep. 24 V
feed output
for
I/O mod-
ules
Evaluation of
line short
circuit
can be selected
as
fault or
alarm
Always just
1
T-branch
between 2
devices
E3M080
E3M071
E3M111
E3M060
Z1I030/050
Z1I020/040
Z1I060/070
(only for CH)
Z1I060/070
E3M171
E3M120
E3M141
Z1I100/110