Operating instructions
Œ•Ž
81
Building Technologies
A6V10225450_b_en_--
Fire Safety
2017.09.07
Reading EVENT MEMORY
What types are
available?
The event memory is available at the following levels:
·
Area
·
Station
What is the
difference?
·
Only area-specific messages are displayed at AREA level.
Regardless of the section in which the event memory is read,
all
area-specific messages are
always displayed (e.g. messages of all sections in this particular area).
·
At STATION level,
all
messages of the station selected are displayed (e.g. section-specific
messages
and
messages which are not dependent on section, such as logging in/out, power
supply messages or messages of other function units).
Operating ac-
cess
If you still don't have operating access when starting operation work, the release procedure is
automatically called up.
Reading event
memory for a
AREA
Perform the following steps to read the event memory at AREA level, e.g. for one fire section:
Step
Action
Result / Comment
1
Navigate
to the AREA you want using:
<Operate..>
t
<Browse..>
t
<Browse FIRE DETECTION..>
Use the scroll keys on the display
2
Press
softkey
<Poll EVENT MEMORY..>
3
Press
softkey
<ALL messages>
- or -
<ALARM messages>
- or -
<FAULT messages>
- or -
<ISOLATION messages>
- or -
<INFORMATION messages>
- or -
<TEST ALARM messages>
4
Set the FROM-TO area
by entering the
time and date
- and -
press <
ü
>
,
to start the search
The
<Next field>
softkey can be used to move the
cursor.
5
Press
softkey
<Print>
·
If a printer is fitted and you
want a print-out.
·
Press the
<Abort printout>
softkey to stop the print-out
Содержание AlgoPilot B3Q661
Страница 84: ......