6 The settings in detail
2014-07-30
Building and room model
Line no.
Operating line
6110
Time constant building
When the outside temperature varies, the room temperature changes at different rates,
depending on the building's thermal storage capacity.
The above setting is used to adjust the response of the flow temperature setpoint to
varying outside temperatures.
·
Example:
> 20
The room temperature will respond more
slowly
to outside temperature variations.
10 - 20
This setting can be used for most types of buildings.
< 10
The room temperature will respond more
quickly
to outside temperature variations.
Frost protection plant
Line no.
Operating line
6120
Frost protection plant
The pumps are activated depending on the
current
outside temperature, even if there
is no request for heat.
Outside
temperature Pump
Diagram
...-4 °C
Continuously on
ON
-5...1.5 °C
On for 10 minutes at 6-hour intervals
takt
1.5°C...
Continuously off
OFF
-2
2
3
7
1
Z
3
0
TA °C
OFF
0
1
2
3
4
-3
-4
-5
-6
-1
takt
ON
Sensor state
Line no.
Operating line
6200
Save sensors
At midnight, the basic unit saves the states at the sensor terminals.
If, after storage, a sensor fails, the basic unit generates an error message.
This setting is used to ensure immediate saving of the sensors. This becomes a
requirement when, for instance, a sensor is removed because it is no longer needed.
parameter reset
Line no.
Operating line
6205
Reset to default parameters
All parameters can be reset to their default values. Exempted from this are the following
operating pages: Time of day and date, operator section, radio communication, and all
time programs.
Plant diagrams
Line no.
Operating line
6212
Check no. heat source 1
6215
Check no. storage tank
6217
Check no. heating circuits