6 The settings in detail
2014-07-30
Evaporation temperature of medium
Line no.
Operating line
3860
Evaporation heat carrier
If there is a risk of the heat carrying medium evaporating due to high collector
temperatures, the collector pump will be deactivated to prevent it from exceeding
certain temperature levels. This is a protective pump function.
6.7 DHW storage tank
Charging control
Line no.
Operating line
5020
Flow setpoint boost
5022
Type of charging
With
B3
With B3/B31
With B3, legio B3/B31
The DHW request to the boiler is made up of the current DHW setpoint plus the
adjustable charging boost.
The storage tank can be charged using up to 2 sensors.
It is also possible to combine partial charging with 1 sensor and the legionella function
with 2 sensors (setting 3).
Overtemperature protection
Line no.
Operating line
5050
Charging temperature max
Solar energy charges the DHW storage tank up to the adjusted maximum DHW
charging level.
The protective collector overtemperature function can reactivate the collector pump
until the maximum storage tank temperature is reached.
recooling
Line no.
Operating line
5055
Recooling temperature
5056
Recooling boiler/HC
5057
Recooling collector
Off
Summer
Always
For recooling the DHW storage tank, there are 2 functions available:
·
Heating energy can be drawn off either by space heating or the DHW storage tank.
This can be selected separately for each heating circuit (operating page “Heating
circuit 1…“)
·
If the collector is cold, the energy can be emitted to the environment via the
collector’s surfaces
Electric immersion heater
Line no.
Operating line
5060
El imm heater optg mode
Substitute
Flow setpoint boost
Type of charging
Recooling heat gen/HC
Recooling collector