Operation and Installation Instructions

Model AE-30U

Alarm Extender Modul

e

Fire Safety

Operation

The 

SIEMENS

 Model AE-30U Alarm Extender

Module is designed to provide one Style Y (Class

B) super-vised notification appliance circuit,

utilizing polarized, parallel connected notification

appliances. Actuation of the module is caused by

high-going DC input signal between 12 and 24 volts

above system common. Dual input activation termi-

nals are provided to facilitate programming.
The Model AE-30U contains a yellow LED trouble

indicator to display open or shorted alarm lines

except when that particular module is not in an

activated condition.
The yellow LED can be lamp tested from the

system control panel.

Installation

1. Mount the module to the horizontal mounting

brackets in the control enclosure.

2. Install the Model JA-5 (5 in. long) bus connector

cable assembly between receptacle P2 of the

module and receptacle P1 of the module or

control panel immediately preceding it in the

bus.

Note

: If the preceding module is on another

row in the enclosure, a JA-24 (24 in.

long) bus connector cable assembly will

be required.

3. Modules are to be bus-connected from right to

left. For two-row enclosures, the modules in the

lower row are to be connected from left to right.

Succeeding rows are to be alternately con-

nected, right to left, left to right, etc.

4. If a module is the last module in the system,

install either a JS-30 (30 in. long) or JS-64

(64 in. long) bus connector assembly from the

unused receptacle of the last module to

terminal 41 of the CP-35 control panel. This

completes the module supervision circuit.

5. If a DC notification appliance circuit is to be

used, install a JP-D program plug into

receptacle P2 of the CP-35 control panel.

Note:

If a battery charger/transfer module is

used, the program plug is not

necessary.

If an AC notification appliance circuit is to

be used, install a JP-A program plug into

receptacle P2 of the control panel.

Note:

When a JP-A program plug is used, an

EL-32 end of line device is required for

the notification appliance circuit.

6. Wire the circuits as described in the 

MODEL

CP-35 CONTROL PANEL INSTALLATION

AND MAINTENANCE INSTRUCTIONS, 

P/N

315-085063 and the 

CP-35 WIRING DIAGRAM,

P/N 315-084902. The maximum line resistance

should be 3 ohms, and a minimum of 14 AWG

wire is recommended. All wiring should comply

with the local and national codes that apply to

the particular installation.

Operational Test

Refer to INSTALLATION AND WIRING in the

Instruction Manual (P/N 315-085063) for the

control panel.

Troubleshooting

Refer to TROUBLESHOOTING THE CP-35 in the

Instruction Manual for the control panel.

Siemens Building Technologies, Inc.

8 Fernwood Road

Florham Park, New Jersey 07932

Siemens Building Technologies, Ltd.

2 Kenview Boulevard

Brampton, Ontario L6T 5E4 CN