See the
ION Reference
, available from www.usa.siemens.com/pds, for more
information.
Related Topics
Alarm and status LED indicators
Configuring LED energy pulsing using ION Setup
You can configure your meter’s energy pulsing LEDs for energy pulsing using ION
Setup.
1. Start ION Setup.
2. Open the Setup Assistant for your device.
3. Select
LED pulsing
.
4. Select the tab that corresponds to the energy pulsing LED you want to
configure.
5. Configure the following basic parameters for your meter’s energy pulsing
LEDs.
Energy pulsing LED parameters available through ION Setup
Parameter
Description
Source
Link this input to the value that you want to pulse on the LED.
Enable
Configuring this setting should only be performed by users with advanced
knowledge of ION, the device template and the power system the device is
connected to.
Int Mode
Specifies the integration mode for the LED (forward, reverse, absolute or
net).
Kt
The amount of source energy required to make the LED pulse.
Pulse Width
The minimum time in seconds between LED pulse transitions.
Pulser Mode
Select when the energy pulsing LEDs will pulse:
•
Always: the energy pulsing LEDs are always pulsing based on their
energy source value.
•
Test Only: the energy pulsing LEDs will only pulse when the meter is
in test mode.
Pulse ovrld
Pulsing normally indicates that the energy pulsing LED should be
operating normally.
Pulsing suspended indicates that the energy pulsing LED is not able to
pulse quickly enough. Modify the Kt value to decrease the number of
energy pulses or decrease the pulse width, if supported by the device
collecting pulses.
NOTE:
To perform specialized configuration go into the advanced mode
of ION Setup and modify, disable or add a new Calibration Pulser module.
These are advanced procedures that should only be performed if you
have advanced knowledge of ION and the power system your meter is
connected to.
See the
ION Reference
, available from www.usa.siemens.com/pds, for
more information.
Configuring digital output energy pulsing using ION Setup
You can configure your meter’s onboard digital outputs for energy pulsing using
ION Setup
Ensure that the digital output port is available for energy pulsing and not
associated with another function.
7EN05-0390-00
85