10. Configure your meter to log the input metering data if required.
Parameter
Description
Pulse Weight
Enter the value per pulse.
Units
Select the measurement units associated with the pulse.
NOTE:
Include source identification information by entering “@”
followed by the source identifier.
Demand Period
Enter the frequency in minutes that input metering data is calculated in
your energy management system.
Rate
Select the rate associated with the defined Units.
Scaling
Select the scaling value based on the relationship between Units and Rate.
Time Base
Select the value and units to match the Rate.
Digital outputs
Digital output applications
Digital outputs are typically used in switching applications, for example, to provide
on/off control signals for switching capacitor banks, generators, and other external
devices and equipment.
The digital output can also be used in demand synchronization applications,
where the meter provides pulse signals to the input of another meter to control its
demand period. The digital output can also be used in energy pulsing applications,
where a receiving device determines energy usage by counting the kWh pulses
coming from the meter’s digital output port.
Related Topics
Configuring onboard digital outputs using ION Setup
You can use ION Setup to configure your meter’s digital outputs.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to
Onboard I/O > Digital Outputs
and select a digital output tab.
82
7EN05-0390-00
Содержание 9810 Series
Страница 1: ...9810 series User manual 7EN05 0390 00 09 2018 www usa siemens com pds ...