Related Topics
Configuring time information using ION Setup
Configuring onboard digital inputs using ION Setup
You can use ION Setup to configure your meter’s digital inputs.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to
Onboard I/O > Digital Inputs
. The tabs correspond to each
digital input. Click on the tab for the digital input you want to edit.
4. Configure the digital input by selecting the parameter and clicking
Edit
.
5. Once the parameter has been configured, click
OK
to save the setting to the
meter.
Parameter
Value/range
Description
Input Mode
Pulse, KYZ, A/C,
IRIG-B
1
Specifies how the meter processes the
signal:
•
Pulse: the meter counts an entire pulse
(from off-on to on-off) as one input.
•
KYZ: the meter counts a transition
(from off-on or from on-off) as one input.
•
A/C: the meter detects analog signals
where the ON condition is based on the
presence of an AC signal
•
IRIG-B
1
: the meter detects an IRIG-B
time synchronization signal.
Polarity
Inverting/Non-Inverting
Specifies if the signal from the digital port is
inverted or not inverted.
Debounce
0.000 - 1.000
Specifies how long (in seconds) the signal
must remain in a state to be considered a
valid state change.
Assigned Port
Defined by your meter’s
hardware
Your meter’s physical digital input port.
EventLog Mode
Log Off/Log On
Specifies if events generate log entries.
State
OFF/ON
Indicates the status of the digital input.
1
IRIG-B can only be connected to one of the onboard digital inputs, not an option module. You
must also configure your meter’s clock to use IRIG-B time synchronization.
Configuring option module digital inputs using ION Setup
You can configure option module digital inputs using ION Setup.
Digital inputs are available on your meter. You can add more digital inputs using
optional I/O modules.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to
Expansion Modules > Option I/O Modules
and select the
module tab that corresponds to the option module with the digital input you
want to configure.
4. Select the digital input channel and click
Edit
.
The setup screen for that digital input is displayed.
5. Configure the digital input by selecting the parameter and clicking
Edit
.