Configuring your meter as a Modbus master using ION Setup
Supported Modbus features
Your meter supports specific Modbus data classes, data formats, function codes
and commands.
Modbus data classes
Class
Description
Coils
Digital bits that can be read and written to
Input status
Digital bits that can be read
Input registers
16-bit integers that can be read
Holding registers
16-bit integers that can be read and written to
Modbus data formats
Format
Type
# of Modbus registers used
Unsigned 16-bit
Integer
1
Signed 16-bit
Integer
1
Unsigned 32-bit
Integer
2
Signed 32-bit
Integer
2
Unsigned 32B-M10K
Integer
2
Signed 32B-M10K
Integer
2
IEEE float
1
Floating point
2
Packed Boolean for inputs
Integer
1
Packed Boolean for coils
Integer
1
Unsigned 16-bit read/write
Integer
1
Signed 64 bit
Integer
4
1
Meters acting as Modbus masters support two versions of IEEE float with different word orders:
high/low = Big Endian, low/high = Little Endian.
16-bit data (one word) is transmitted with most-significant byte first and least-
significant byte second.
32-bit data (two words) is transmitted with the most-significant word first and the
least-significant word second.
Modbus function codes
Function
Description
Master/slave
1
Read coil status
Master and slave
2
Read input status
Master and slave
3
Read holding registers
Master and slave
4
Read input registers
Master
5
Write to a coil
Master
6
Write to a holding register
Master and slave
15
Write to multiple coils
Master
16
Write to multiple holding registers
Master and slave
17
Report slave ID (serial only)
Master and slave
50
7EN05-0390-00