3. Select a protocol from the list and click
Edit
.
4. Select the
Enabled
checkbox to enable the port. Clear the checkbox to
disable the port.
NOTE:
The IEC61850 port is enabled when a valid CID file is uploaded to
the meter. The port is disabled by removing the CID file.
NOTE:
For EtherGate functionality, the EtherGate protocol must be
enabled and the applicable serial port set to
EtherGate
.
5. Select a port number from the
Port Number
dropdown list or by clicking in the
Port Number
field and entering a port number.
6. Click
OK
.
If multiple ports are set to the same number, ION Setup responds with a
message indicating that the port is already in use by another protocol.
NOTE:
When configuring the FTP ports, the data connection port is
automatically assigned to the command connection port number minus 1.
For example, if the command connection port number is 21, the data
connection port number is automatically set to 20.
Network protocol control using the meter webpages
Use the meter webpage to enable, disable or change the port number of the
network protocols supported on your meter.
The Setup tab contains configurable elements for enabling, disabling and
changing the port numbers for your network protocols.
When configuring communications parameters, ensure you maintain at least one
communication path that allows full access to your device; otherwise you may
permanently lose the ability to change your device’s configuration and access to
additional data.
NOTICE
LOSS OF ACCESS
Failure to follow these instructions can result in loss of access to the
device.
Ensure you maintain sufficient access to communicate with and configure your
device.
1. Open a web browser and enter your meter’s IP address in the address box.
The webpage login is displayed.
2. Enter your login credentials.
3. Navigate to
Setup > Ethernet
.
4. Click
Advanced Settings
at the bottom of the screen.
5. Select YES or NO to enable or disable each configurable protocol.
6. Enter the port number for each configurable protocol.
7. Click
Apply
to send these settings to your meter.
Network protocol control using the meter display
The Ethernet Port Enable Setup allows you to enable or disable your network
protocols through your meter’s display.
When configuring communications parameters, ensure you maintain at least one
communication path that allows full access to your device; otherwise you may
permanently lose the ability to change your device’s configuration and access to
additional data.
38