Configuring Syslog network settings using ION Setup
You can configure your syslog settings using ION Setup.
1. Open the Setup Assistant for your meter. See the ION Setup Help for
instructions.
2. Select
Communications
>
Advanced Ethernet
and click the
SysLog
tab.
3. Select
Enable Syslog
and click
Edit
.
4. Select
Yes
to enable the syslog server feature or select
No
to disable it.
5. Click
OK
.
6. Select
Syslog Server
and click
Edit
.
7. Enter the IPv4 address or an IPv6 address for the syslog server.
You must enter the IP address for the syslog server, not the server’s fully-
qualified domain name.
8. Click
OK
.
9. Verify that the Syslog server is receiving log information from the meter.
NOTE:
If the
Enable Syslog
register is enabled but the
Syslog Server
register does not contain an IP address, an event is generated in the
event log to indicate that syslog is enabled with no server IP.
Related Topics
Syslog severity to event log priority mapping
Syslog severities map to ION event priorities (0-255).
Only four of the syslog severities are used in the mapping.
Syslog severity
ION event priority name
ION event priority range
2 - Critical condition
High
192-255
4 - Warning condition
Medium
128-191
5 - Normal but significant
condition
Low
64-127
6 - Informational
None
0-63
Advanced log setup and memory optimization
You can configure your meter’s logs to help ensure the integrity of critical data and
to optimize the meter’s memory usage.
Before you configure your meter’s logs, it is important to understand how logging
functions and how the settings work together.
NOTE:
Configuring your meter’s logs requires an in-depth understanding of
the meter’s memory, how the logs function and the data you are capturing.
Viewing log configuration and memory usage information
You can use ION Setup to view log settings and memory usage information for
your meter’s default logs.
This information can help you understand your log usage and how to optimize
your logging configuration for your situation.
168
7EN05-0390-00