5. Configure the parameters as required.
Transient setup parameters
Parameter
Value/Range
Description
Enabled/Disabled
Enabled or Disabled
Specifies if transient recording and alarming is enabled.
Nominal
1 to 999,999
Specifies the nominal voltage value used for transient detection.
Threshold
Percentage of nominal
Specifies the threshold expressed as a percentage of the nominal voltage, plus
100.
For example, if you want transients recorded when voltage deviates from nominal
by 20%, enter 120.
Alarm priority
See description
Select the alarm priority you want to associate with Transient alarms.
To stop an alarm from being displayed without affecting other meter features, set
the alarm priority to Info Only.
Configuring digital input alarms using ION Setup
You can use ION Setup to configure the digital alarm settings.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to
Alarming > Digital Input
.
4. Configure the digital input alarm settings by selecting an input and clicking
Edit
. Some settings are not configurable and are grayed out.
5. Click
Save
to save the changes to the meter.
Parameter
Value/Range
Description
Input
Input On/Input Off
Specifies the input state/alarm behavior:
•
Input On: the alarm is on when the digital input is on.
•
Input Off: the alarm is on when the digital input is off.
Force Off
Checked/Unchecked
Forcing the alarm off disables all functions of the associated input.
To stop an alarm from being displayed without affecting digital input features, set
the alarm priority to Info Only.
Label
String value
When available, lets you modify the default label so it more clearly identifies the
alarm. Letters, numbers, and underscores are permitted.
Alarm Priority
None, Info Only, Low,
Medium or High
Specifies the priority level of the digital input alarm. To disable the alarm, set
priority to Info Only.
Custom Priority
0-255
Select custom priority to view and configure the event priority of the event
associated with the alarm. The event log cutoff value is displayed for reference;
event priorities above the cutoff are stored in the meter’s event log.
Alerting
An alert is an external notification from the meter to indicate changes, for example,
a change of state for a digital input, or a power quality event such as a sag or
swell.
When an alert condition occurs, a pulse or trigger is sent and generates the alert.
You can configure alerts to send notification emails or messages to your energy
management system through your meter’s existing Ethernet communications
connections. You can configure alert messages as a simple text string or you can
also include device information. You can configure the alert’s priority so that alerts
are also recorded in the meter’s event log.
You can configure multiple alerts on a single meter, each having different
activation triggers, messages and/or transmission types. For instance, you can