7. Click
Save
to save the settings to your meter.
Parameter
Value/Range
Description
By Percentage
By Percentage/By Value
When available, specifies if the Pickup and Dropoff entries are by percentage or
by value. If the option is not available, pickup and dropoff entries are by value.
Force Off
Checked/Unchecked
Forcing the alarm off disables all functions of the associated input.
To stop an alarm from being displayed without affecting other meter features, set
the alarm priority to Info Only.
Label
String value
When available, lets you modify the default label so it more clearly identifies the
alarm. Letters, numbers, and underscores are permitted.
Pickup
Numeric value
Use this setting to provide a value for when the alarm turns on.
Pickup Delay
Numeric value
This specifies the number of seconds the input must be over the alarm pickup
value before the alarm turns on.
Dropout
Numeric value
Use this setting to provide a value for when the alarm turns off.
Dropout Delay
Numeric value
This specifies the number of seconds the input must be below the alarm dropoff
value before the alarm turns off.
Alarm Priority
None, Info Only, Low,
Medium or High
Specifies the priority level of the standard alarm. When priority is set to Info Only,
the alarm does not appear on the display.
Custom Priority
0-255
Select custom priority to view and configure the event priority of the event
associated with the alarm. The event log cutoff value is displayed for reference;
priorities above the cutoff are stored in the meter’s event log.
Sag/swell overview
Your meter monitors your power system’s voltage and current for sags and swells
(INCITS (CBEMA) Type 2 and Type 3 disturbances); it then reports the
disturbance’s magnitude and duration.
You can manually enter the limits (criteria) used by the meter to identify a sag or
swell, or you can have your meter learn sag/swell limits by monitoring your power
system.
Related Topics
Configuring Sag/Swell logging using ION Setup
Configuring sag/swell alarms using ION Setup
You can use ION Setup to configure the sag/swell alarm settings.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to
Alarming > Sag/Swell
.
4. Select the parameter you want to configure and click
Edit
.
The setup dialog box for that parameter appears.
130
7EN05-0390-00