Installation and Wiring
9510 and 9610 I/O Card
Page 2
Installation and Wiring
D
ANGER
During normal operation of the meter, hazardous voltages are present which can cause severe injury or
death. These voltages are present on the terminal strips of the device and throughout the connected
potential transformer (PT), current transformer (CT), status input, relay, and control power circuits. Only
qualified, properly trained personnel should perform installation and servicing.
The standard model I/O card has 8 digital inputs. Depending on what you ordered,
the I/O card will also contain either 4 analog inputs, or 4 analog outputs, or both.
Check the label on the I/O card for your I/O specifications.
AI4
AO4
AI3
A03
AI2
A02
AI1
AO1
Rear View of Meter
Analog connections from
external transducers
0 to 20 mA or 0 -1 mA
Analog Connections to
analog transducers
0 to 20mA: 500 Ohm load Max
-1 to 1mA: 10k Ohm load Max
Digital connections from
external relays or pulse counter
50 VDC Max
External Dry Contacts
(polarity for SSR
contacts shown)
AWG 12 to 14 (3.3 to 2.1 mm ) recommended; wire sizes will vary depending on application
2
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
DICOM
AI1
+
-
AO1
OUTCOM
I/O C
ARD
Standard I/O Locations