7 | Installation
98/174
8DJH • Installation and Operating Instructions • Version 11 • 500-8384.9
3. Mount the cross member in the metering panel [
Page 126, "Removing and mounting the
4. Mount the cable compartment covers in the metering panel [
mounting the cable compartment cover"].
7.20.9 Mounting earthing accessories in the metering panel
DANGER
Live parts
Touching live parts leads to a life-endangering electric shock. Observe the Five Safety Rules:
⇨ Isolate.
⇨ Secure against reclosing.
⇨ Verify safe isolation from supply.
⇨ Earth and short-circuit.
⇨ Cover or barrier adjacent live parts
DANGER
Unsuitable earthing accessories
Any use of inappropriate earthing accessories for remote cable compartment cover can
cause serious injury or death due to an internal arc.
☒ Please observe the manufacturer information and suitability of the earthing accessories.
⇨ The earthing accessories must be designed for the short-circuit currents of the
respective grid configuration.
⇨ The connections of the earthing accessories must be suitable for installation at the
switchgear.
DANGER
Incorrectly mounted connecting element
A connecting element on the earthing set which is not screwed flat to the earthing
connection leads to an insufficient current carrying capacity of the earthing. In the case of
remote cable compartment cover can cause serious injury or death due to an internal arc.
⇨ Bolt the connecting element of the earthing accessories flush to the earthing
connection.
INFORMATION
Before mounting the earthing accessories, read the manufacturer's assembly instructions.
The earthing accessories are not supplied by the factory. Tested earthing accessories
[
Page 100, "Mounting earthing accessories in the metering panel"].