3 | Description
20/174
8DJH • Installation and Operating Instructions • Version 11 • 500-8384.9
Tab. 7:
Cable plugs for single cable connection (interface type A)
Cable type
Cable plugs
Make
Type
G/W
1)
Conductor
cross-section
[mm
2
]
Design
Thermoplastic-insulated cables ≤ 12 kV according to IEC/EN 60502-2 / VDE 0276-620
1-core cable, PE- and XLPE-
insulated N2YSY (Cu) and
N2XSY (Cu)
or
NA2YSY (Al) and
NA2XSY (Al)
Nexans Euromold
158LR
W
16...120
screened; with capacitive measuring point
152SR
G
95...120
screened; with capacitive measuring point
200LR
W
25...95
screened; with capacitive measuring point
K200LR-12
W
25...95
screened
K200SR-12
G
25...95
screened
nkt cables
EASW 10 / 250, size
2
W
25...95
screened; option: with metal housing or capacitive
measuring point
EASG 10 / 250, size 2 G
25...95
screened; option: with capacitive measuring point
CE 24 – 250
W
95...120
screened; option: with metal housing or capacitive
measuring point
Südkabel
SEHDG 11.1
G
25...120
screened; option: with metal housing
SEW 12
W
25...120
screened; option: with metal housing
Cooper Power Sys-
tems
DE 250 – R-C
W
16...120
screened
DS 250 – R-C
G
16...120
screened
Prysmian Kabel und
Systeme (Pirelli Elek-
trik)
FMCE-250
W
25...120
screened
3M Deutschland
93-EE 605-2 / -95
W
25...95
screened; option: with metal housing
93-EE 600-2 / xx
G
25...150
screened; option: with metal housing
TE Connectivity
RSSS 52xx
G
25...95
screened; with capacitive measuring point
RSES 52xx-R
W
25...120
screened; with capacitive measuring point
Thermoplastic-insulated cables 15 / 17.5 / 24 kV according to IEC / EN 60502-2 / VDE 0276-620
1-core cable, PE- and XLPE-
insulated N2YSY (Cu) and
N2XSY (Cu)
or
NA2YSY (Al) and
NA2XSY (Al)
Nexans Euromold
K158LR
W
16...120
screened; with capacitive measuring point
K152SR
G
25...120
screened; with capacitive measuring point
200LR
W
25...95
screened; with capacitive measuring point
K200LR-16
W
25...95
screened
K200SR-16
G
25...95
screened
nkt cables
EASG 20 / 250
G
25...95
screened; option: with metal housing
CE 24 – 250
W
25...95
screened; option: with metal housing or capacitive
measuring point
Südkabel
SEHDG 21.1
G
25...70
screened; option: with metal housing
SEW 24
W
25...95
screened; option: with metal housing
Cooper Power Sys-
tems
DE 250 – R-C
W
16...120
screened
DS 250 – R-C
G
16...120
screened
Prysmian Kabel und
Systeme (Pirelli Elek-
trik)
FMCE-250
W
25...120
screened
3M Deutschland
93-EE 605-2 / -95
W
25...95
screened; option: with metal housing
93-EE 600-2 / xx
G
25...150
screened; option: with metal housing
TE Connectivity
RSSS 52xx
G
16...70
screened; with capacitive measuring point
RSES 52xx-R
W
16...120
screened; with capacitive measuring point
1)
G = straight cable plug, W = cable elbow plug
3.8.4 Single cable connection with voltage transformer 4MT8 (interface type C)
The voltage transformer 4MT8 can be installed in ring-main feeders and circuit-breaker feeders
with a panel width of 500 mm. A deep cable compartment cover is not necessary.
For connection, symmetrical cable T-plugs (see table) are required. Before performing a voltage
test at the cables (on site with max. 80% U
d
), the voltage transformers must be removed.