9 | Operation
156/174
8DJH • Installation and Operating Instructions • Version 11 • 500-8384.9
INFORMATION
The following descriptions do not substitute reading the manufacturer documentation.
⇨ Before using the voltage indicators, read the manufacturer documentation. The
manufacturer documentation is considered as leading.
INFORMATION
In adverse light conditions, shield the display of the voltage indicator or illuminate it
additionally.
Use
Voltage indicators type HR or LRM are used for verification of safe isolation from supply on
capacitive HR or LRM interfaces according to IEC 61243-5. There, the voltage indicator is the
mobile part of a voltage detecting system.
▪ The "voltage present" indication is ensured within the specified operating temperature in the
voltage range of the interface according to IEC 61243-5 Table 1.
▪ Voltage indicators can be used indoors and outdoors.
▪ Store and transport voltage indicators in dry and clean condition.
Maintenance
Voltage indicators do not contain any parts replaceable by the user, and they are maintenance-
free.
Overview
2018
Fig. 181:
Voltage indicator
1
Inscription on the upper and lower side:
Type designation, year of manufacture, and
test symbol
2
Plug
3
Indication
XXXXXXXXXXXXXXX
XXXXXXXXXXXXXXX
XXXXXXX X XXX
XXXXXXX
XX
Fig. 182:
Coupling section and inserted voltage
indicator
1
Inserted voltage indicator
2
Capacitive test socket (coupling sec-
tion)
3
Earth socket (coupling section)
4
Cover
5
Printing: Repeat test of interface
condition
Tab. 50:
Technical data of voltage indicator and coupling section
HR voltage indicator
LRM voltage indicator
Rated voltage
(rated pickup voltage of the interface)
70...90 V
4...5 V
Rated frequency
50 Hz
50 Hz
Input impedance
36.0…43.2 MΩ
2.0…2.4 MΩ
Flashing frequency (at pickup
voltage)
≥ 1 Hz
≥ 1 Hz
Power supply
Power is supplied through the voltage to be tested when the voltage
indicator is inserted.