Installation | 7
109/174
500-8384.9 • Version 11 • Installation and Operating Instructions • 8DJH
7.21.5 Cable installation in switchgear with pressure absorber (IAC up to 16 kA and
21 kA)
Fig. 133:
Switchgear with pressure absorber
for IAC up to 16 kA (example)
Fig. 134:
Switchgear with pressure absorber
for IAC up to 21 kA (example)
1
Cable compartment cover
2
Cross member
3
Front plate of base
1. Remove
1
Page 125, "Removing and mounting the cable
2. Remove
2
the cross member [
Page 126, "Removing and mounting the cross member"].
3.
Only for switchgear with pressure absorber (IAC up to 21 kA):
Remove the front plate
3
of the base. To do this, remove the 6 self-tapping bolts M6x16.
4
High-voltage cable (max.
Ø 52 mm)
5
Nut-and-washer assembly
M8 (2x)
6
Rubber sleeve (Ø 70 mm) for
high-voltage cables
7
Rubber sleeve (Ø 56 mm) for
control cables
8
Front floor plate
9
Control cables (max. Ø 38 mm)
10
Fixing point of foundation
11
Slot for the lug of the cross
member
Fig. 135:
Cable installation in switchgear with pressure absorber (IAC up to
16 kA)
Fig. 136:
Cable installation in switchgear with pressure absorber (IAC up to
21 kA)