7 | Installation
104/174
8DJH • Installation and Operating Instructions • Version 11 • 500-8384.9
10. Push the cable plugs
1
to
3
onto the bushings and mount them according to the
manufacturer’s instructions. Observe the phase sequence.
NOTICE! Excessive torque can
cause damage to the bushing. Tighten the cable plug with a torque according to the
manufacturer's instructions (max. 50 Nm).
11. Mount the upper part of the cable clamps
6
.
12. Align the cable bracket
5
and bolt it tight.
13. Refit the cross member [
Page 126, "Removing and mounting the cross member"].
14. Connect the earthing cables of the plug housings and the cable shield at the cross
member
7
.
15. Hook the cable compartment cover in again [
Page 125, "Removing and mounting the
✓
The cable connection is completed.
Double cables and surge arresters
Double cables and surge arresters can be connected to the following panel types using the
corresponding plug-in cable systems:
▪ Ring-main panel
▪ Cable panel
▪ Circuit-breaker panel
Please observe the following:
▪ Depending on its type, a double cable connection requires a deep cable compartment cover
and larger floor openings.
▪ Depending on their type, surge arresters also require a deep cable compartment cover.
For further information [
7.21.3 Installing cable plugs type Raychem RICS5xxx with RDA
1. Remove the upper cross member at the panel. To do this, remove 4 self-tapping bolts M6
1
.
Fig. 125:
Removing the upper cross member
2. Mount cable plug type Raychem RICS5xxx with surge arrester RDA
1
. Observe the
installation instructions of the cable plug and surge arrester manufacturer (see order
documents).
Содержание 8DJH
Страница 173: ......