4 Getting Started
4.7 Commissioning
33
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
The device is designed for continuous operation.
If you want to change the interfacing on the device, for example by wiring terminals that have so far not been
used, please observe the above mentioned safety instructions.
4.7.2
Starting the Device with the Default IP Address
SICAM I/O Unit has the following internal default IP address
192.168.0.55
and default subnet mask
255.255.255.0
.
If you have entered a custom IP address during device configuration, you can temporarily activate the internal
default IP address of the device if necessary. For this purpose, press the IP-Addr. push-button on the device
front for at least 3 s.
Figure 4-5
Location of the Push-button for Activating the Default IP Address
When you press the IP-Addr. push-button, SICAM I/O Unit will reset and use the default IP address until you
have set a new IP address or switched the device off and on again.
NOTE
The operation requires JavaScript. If JavaScript is not yet enabled, activate it as described in chapter 6.2.2.
Default IP Address : 192. 168.0.55
Default Subnet Mask : 255.255 .255.0
IP-Addr. push-button for
default IP address
NOTE
Changing the IP address will lead to a device reset, and the LEDs on the top side of the device indicate that
the device was started with the default IP address (see chapter 10.3).
In this case, the parameterized IP address and the default IP address are displayed on the
Information
tab,
Device information
item (see chapter 6.2.5.1).
When the device has started with the default IP address, the factory-set default passwords are also active (see
chapter 6.3.3.9).
MAN_SICAM_IO-Unit_7XV5673_US.book Page 33 Thursday, May 10, 2012 10:59 AM