background image

English

7XV5662-0AA00

30

C53000-B1174-C134-7

Statement of Conformity 

This product complies with the directive of the Council of the European Communities on the
approximation of the laws of the member states relating to electromagnetic compatibility
(EMC Council Directive 89/336/EEC) and concerning electrical equipment for use within
specified voltage limits (Low-voltage Directive 2006/95/EC). 

This conformity has been proved by tests performed according to Article 10 of the Council
Directive in agreement with the generic standards EN 61000-6-2 and EN 61000-6-4 (for
EMC directive) and with the standards EN 60255-6 (for low-voltage directive) by Siemens
AG. 

The device is designed and manufactured for application in industrial environment.

The product conforms with the international standards of IEC 60255 and the German
standards VDE 0435. 

Notes and Warnings 

The warnings and notes contained in this booklet serve for your own safety and for an
appropriate lifetime of the device. Please observe them! 

The following terms are used: 

DANGER 

indicates that death, severe personal injury or substantial property damage will result if
proper precautions are not taken. 

Warning 

indicates that death, severe personal injury or substantial property damage can result if
proper precautions are not taken. 

Caution 

indicates that minor personal injury or property damage can result if proper precautions are
not taken. This is especially valid for damage on or in the device itself and consequential
damage thereof. 

Note 

indicates information about the device or respective part of this booklet which is essential to
highlight. 

Содержание 7XV5662-0AA00

Страница 1: ...uch Manual Bestell Nr Order No C53000 B1174 C134 7 Hinweise für den Gebrauch Deutsch Seite 3 Kommunikationsumsetzer X 21 G 703 1 Synchrone Schnittstelle Directions for use English Page 29 Communication Converter X 21 G 703 1 Synchronous interface ...

Страница 2: ...Deutsch 7XV5662 0AA00 2 C53000 B1174 C134 7 ...

Страница 3: ...nweise und Warnungen 4 Aus und Einpacken des Gerätes 6 Lagerung und Transport 6 Verwendung 7 Merkmale 8 Funktion 9 Anschlüsse 10 Anschlusshinweise 11 Montage 15 Inbetriebsetzung 16 Technische Daten 21 Maßbilder bis Hardwareausgabestand EE 27 Maßbilder ab Hardwareausgabestand FF 28 ...

Страница 4: ...ernationalen Normen der Reihe IEC 60255 und der nationalen Bestimmung VDE 0435 Hinweise und Warnungen Die Hinweise und Warnungen in dieser Anleitung sind zu Ihrer Sicherheit und einer ange messenen Lebensdauer des Gerätes zu beachten Folgende Signalbegriffe und Standarddefinitionen werden dabei verwendet GEFAHR bedeutet dass Tod schwere Körperverletzung oder erheblicher Sachschaden eintreten werde...

Страница 5: ...eile dieser Geräte unter gefährlicher Spannung Es können deshalb schwe re Körperverletzung oder Sachschaden auftreten wenn nicht fachge recht gehandelt wird Nur entsprechend qualifiziertes Personal soll an diesem Gerät oder in dessen Nähe arbeiten Dieses muss gründlich mit allen Warnungen und Instandhaltungsmaßnahmen gemäß dieser Anleitung sowie mit den Sicherheitsvorschriften vertraut sein Der ei...

Страница 6: ...agerung des Gerätes oder zugehöriger Ersatzbaugruppen gilt der Temperaturbereich von 25 C bis 55 C Die relative Feuchte darf weder zur Kondenswasser noch zur Eisbildung führen Es wird empfohlen bei der Lagerung einen eingeschränkten Temperaturbereich zwischen 10 C und 35 C einzuhalten um einer vorzeitigen Alterung der in der Stromversorgung eingesetzten Elektrolytkondensatoren vorzubeugen Außerdem...

Страница 7: ...odul FO5 bedeutet es handelt sich um ein optisches 820 nm Steckmodul im Schutzgerät das eine Taktrückgewinnung aus dem Sendetakt des Kommu nikationsnetzes durchführt Nähere Angaben hierzu siehe SIPROTEC Gerätehandbuch Der Datentransfer zwischen den Schutzgeräten stellt eine Punkt zu Punkt Verbindung dar ist bittransparent und synchron Der Kommunikationsumsetzer unterstützt eine einfache Inbetriebs...

Страница 8: ...er X 21 15 polig oder 5 polige Schraubklemme G 703 Maximale Leitungslänge für die Verbindung Kommunikationsgerät Kommunika tionsumsetzer für X 21 100 m Maximale Leitungslänge für die Verbindung Kommunikationsgerät Kommunika tionsumsetzer für G 703 1 300 m Weitbereichsnetzteil für Gleichspannung 24 V bis 250 V Grenzspannung 19 V bis 300 V und Wechselspannung 115 V bis 250 V Bereich 92 V bis 286 V Ü...

Страница 9: ...lkommen bittransparent d h direktes Weiterleiten der Informationen ohne selbst Informationen hinzuzufügen oder auszublenden Bild 2 zeigt die Hardware Struktur Die Einstellung der Schnittstellenart wahlweise X 21 oder G 703 1 und der gewünschten Übertragungsgeschwindigkeit erfolgt manuell über Steckbrücken Jumper Eine weitere Steckbrücke dient der Umschaltung auf Testbetrieb für die Inbetriebsetzun...

Страница 10: ...G 703 1 Die Signale der G 703 1 Schnittstelle sind auf die 5 polige Schraubklemme G 703 aufzulegen jeweils ein kommendes und ein gehendes Adernpaar Die links daneben liegende fünfte Schraubklemme S dient zum Auflegen des Kabelschirms und ist mit dem Gehäuse verbunden Die G 703 1 Signale sind von den anderen elektrischen Kreisen galvanisch getrennt Bild 2 LWL Die LWL Schnittstellen dienen zur Anbin...

Страница 11: ...und entsprechen der genormten Pulsmaske Stromversorgung Die Hilfsspannung ist an der 2 poligen Schraubklemme 24 250 VDC 115 250 VAC aufzulegen Die zulässigen Werte und Toleranzen finden Sie in den Technischen Daten Seite 21 Der rechts danebenliegende Erdungsanschluss ist mit dem Schutzleiter Erde zu verbinden Anschlusshinweise Schraubklemmen der Anschlussleisten Die Klemmschrauben sind als Schlitz...

Страница 12: ...n Datenkabel vom Kabeltyp S UTP Screened Unshielded Twisted Pair sein Ein S UTP Kabel besteht aus einem Kunststoffmantel und einem Gesamtschirm in dem sich die paarweise verseilten Adernpaare befinden Die Schirmung darf aus Kupfergeflecht oder Aluminiumfolie oder aus beidem bestehen Es können auch Kabel vom Typ S FTP Screened Foil Twisted Pair verwendet werden bei denen die paarweise verseilten Ad...

Страница 13: ...100 m betragen Zwischen Kommuni kationsumsetzer und X 21 Schnittstelle des Kommunikationsgerätes werden kurze Verbin dungen empfohlen um elektrische Störbeeinflussungen zu vermeiden Der Kommunikati onsumsetzer sollte in der Nähe des Kommunikationsgerätes DÜE installiert werden Bitte die zusätzliche Installationsanweisung beachten Bild 6 Pinbelegung des 15 poligen Datenkabels auf der Geräteseite X ...

Страница 14: ...nehmen Bild 7 LWL Anschlüsse für Sende und Empfangsrichtung LWL Stecker Typ ST Stecker zu verwendender Faser Typ Multimode LWL G62 5 125 µm empfohlen Wellenlänge λ ca 820 nm Zulässige Biegeradien für Innenkabel rmin 5 cm für Außenkabel rmin 20 cm Hinweis Die Klasse 1 nach EN 60825 1 wird bei Fasertyp G62 5 125 µm eingehalten LWL 1 kanalig Warnung Nicht direkt in die Lichtwellenleiter elemente scha...

Страница 15: ...sumsetzers Im Bild 3 sehen Sie wo sich der Schnittstellenstecker befindet Bild 6 zeigt die Anschlussbelegung am DEE Anschluss des Kommunikationsumsetzers Stecken Sie das andere Ende des Kabels in das von Ihnen gewählte Kommunikati onsgerät Achten Sie unbedingt auf die korrekte Verdrahtung zwischen den Schnittstellen Bei Verwendung der G 703 1 Schnittstelle Schließen Sie mittels Schraubendreher die...

Страница 16: ...tel lenart ein X30 in Stellung 1 2 für Schnittstelle X 21 X30 in Stellung 2 3 für Schnittstelle G 703 1 Auswahl der Übertragungsgeschwindigkeit Stellen Sie mittels Jumper für X20 X22 X24 und X26 die für die Kommunikation erforderliche Übertragungsgeschwindigkeit ein s Tabelle 1 Es kann nur ein Steckplatz gleichzeitig gesteckt werden Hinweis In der Betriebsart G 703 1 muss der Jumper auf X20 stecke...

Страница 17: ...n gedacht In dieser Betriebsart durchlaufen keine Signale den Kommunikationsumsetzer Bild 9 Die vorhandenen Schnittstellen werden an den Eingängen geloopt so dass sich damit Teile der gesamten Kommunikationsstrecke prüfen lassen Im Testmodus ist das GOK Relais angezogen Weitere Einzelheiten über das Vorgehen bei der Inbetriebsetzung eines Schutzgerätes mit dem Kommunikationsumsetzer entnehmen Sie ...

Страница 18: ...olge zusammenzuschrauben Der Deckel des Umsetzers ist mit 6 Schrauben zu befestigen und die Hilfsspannung wieder anzulegen Anzeige und Bedienung Es sind vier Anzeige und ein Bedienelement am KU XG vorhanden Im einzelnen handelt es sich um eine rote zwei gelbe eine grüne LED und einen Taster die sich auf der Oberseite des Gehäuses befinden LED1 Error Die rote LED Error signalisiert unmittelbar die ...

Страница 19: ...sierungselemente auf Funktionsfähigkeit möglich In den folgenden sechs Schritten sind die LED Zustände während der Ausführung einer Inbetriebnahme dargestellt Aufbau siehe Bild 1 Darin bedeutet einen undefinierten beliebigen LED Zustand AN AUS BLINKT Voraussetzungen der Inbetriebnahme Die Jumperpositionen müssen in beiden KU XG s KU XG1 KU XG2 der gewünschten Betriebsart Baudrate entsprechen Schri...

Страница 20: ...tt 4 KU XG2 Power On KU XG1 KU XG2 LED1 AUS LED1 EIN LED2 LED2 LED3 BLINKT LED3 LED4 EIN LED4 EIN Schritt 5 Am KU XG2 die Schnittstelle X 21 G 703 auflegen KU XG1 KU XG2 LED1 AUS LED1 AUS LED2 LED2 BLINKT LED3 BLINKT LED3 LED4 EIN LED4 EIN Schritt 6 Am KU XG2 die LWL Kabel anschließen Schutzkommunikation starten KU XG1 KU XG2 LED1 AUS LED1 AUS LED2 BLINKT LED2 BLINKT LED3 BLINKT LED3 BLINKT LED4 E...

Страница 21: ...chluss der Hilfspannung 50 ms Wechselspannung Melderelais GOK Kontakt 1 Wechsler Schaltleistung EIN 1000 W 1000 VA AUS 40 W 30 VA induktiv Schaltspannung 250 V zulässiger Strom pro Kontakt 5 A dauernd 30 A für 0 5 s Nennhilfsgleichspannung UH 24 V bis 250 V zulässige Spannungsbereich 19 V bis 300 V Leistungsaufnahme ca 3 5 W Nennhilfswechselspannung UH 115 V bis 250 V 50 60 Hz zulässige Spannungsb...

Страница 22: ...berbrückbare Entfernung max 100 m 512 kBit s Übertragungsrate 64 kBit s oder 128 kBit s oder 256 kBit s oder 512 kBit s einstellbar Kabel siehe Installationsanweisung G 703 1 Anschluss 5 polige Schraubklemme potentialfrei überbrückbare Entfernung max 300 m Übertragungsrate 64 kBit s Prüfspannung 500 V 50 Hz Kabel siehe Installationsanweisung Elektrische Prüfungen Vorschriften Normen IEC 60255 Prod...

Страница 23: ...5 22 2 Klasse IV und beide Polaritäten 150 pF Ri 330 Ω IEC 61000 4 2 Klasse IV Bestrahlung mit HF Feld 10 V m 80 MHz bis 1000 MHz 80 AM Frequenzdurchlauf 1 kHz IEC 60255 22 3 Klasse III 20 V m 1 4 GHz bis 2 0 GHz 80 AM 1 kHz IEC 61000 4 3 Klasse III 10 V m 800 MHz bis 960 MHz 80 AM 1 kHz Bestrahlung mit HF Feld Einzelfrequenzen IEC 60255 22 3 IEC 61000 4 3 Kl III 10 V m amplitudenmoduliert 80 160 ...

Страница 24: ...tand Capability 2 5 kV Scheitelwert 1 MHz τ 15 ms IEEE Std C37 90 1 400 Stöße je s Prüfdauer 2 s Ri 200 Ω Fast Transient Surge Withstand Capability 4 kV 5 50 ns 5 kHz Burstlänge 15 ms IEEE C37 90 1 Wiederholrate 300 ms beide Polaritäten Für GOK Relais in der Betriebsart G703 1 Ri 50 Ω Prüfdauer 1 min bis zu einem Störpegel von 3 kV Radiated Electromagnetic Interference 35 V m 80 MHz bis 1000 MHz I...

Страница 25: ...rizontale Achse 1 Hz bis 8 Hz 1 5 mm Amplitude vertikale Achse 8 Hz bis 35 Hz 1 g Beschleunigung horizontale Achse 8 Hz bis 35 Hz 0 5 g Beschleunigung vertikale Achse Frequenzdurchlauf 1 Oktave min 1 Zyklus in 3 Achsen senkrecht zueinander Schwing und Schockbeanspruchung beim Transport Normen IEC 60255 21 und IEC 60068 2 Schwingung sinusförmig IEC 60255 21 1 Klasse 2 5 Hz bis 8 Hz 7 5 mm Amplitude...

Страница 26: ... 40 C bis 85 C Lagerung und Transport mit werksmäßiger Verpackung Feuchte zulässige Feuchtebeanspruchung im Jahresmittel 75 relative Feuchte an 56 Tagen im Jahr bis zu 93 relative Feuchte Betauung im Betrieb unzulässig Die Geräte sind so anzuordnen dass sie keiner direkten Sonneneinstrahlung und keinem starken Temperaturwechsel bei dem Betauung auftreten kann ausgesetzt sind Konstruktive Ausführun...

Страница 27: ...abestand EE Bild 10 Abmessungen des Kommunikationsumsetzers bis Hardwareausgabestand EE An der Wand montierte Hutschiene gehört nicht zum Lieferumfang Entriegelung 1 Hutschienenmindestlänge 2 Maßbild gilt für Hutschiene IEC EN 60715 35 x 7 5 Maße in mm Kreuzschlitzschraube ...

Страница 28: ... 5 69 8 14 5 An der Wand montierte Hutschiene gehört nicht zum Lieferumfang Kreuzschlitzschraube Entriegelung Hinweis Bitte beachten Sie dass es kleine Unterschiede in den Abmessungen bei Ge räten ab Hardwareausgabestand FF gegenüber Geräten bis einschließlich Hardwareausgabestand EE gibt Maße in mm 1 Hutschienenmindestlänge Maßbild gilt für Hutschiene IEC EN 60715 35 x 7 5 ...

Страница 29: ...arnings 30 Unpacking and Re packing 32 Storage and Transport 32 Application 33 Features 34 Function 35 Connections 36 Connection Instructions 37 Installation 41 Commissioning 42 Technical Data 47 Dimensioned drawings up to hardware version EE 54 Dimensioned drawings from hardware version FF 55 ...

Страница 30: ...lication in industrial environment The product conforms with the international standards of IEC 60255 and the German standards VDE 0435 Notes and Warnings The warnings and notes contained in this booklet serve for your own safety and for an appropriate lifetime of the device Please observe them The following terms are used DANGER indicates that death severe personal injury or substantial property ...

Страница 31: ...e present in this electrical equipment during operation Non observance of the safety rules can result in severe personal injury or property damage Only qualified personnel shall work on and around this equipment after becoming thoroughly familiar with all warnings and safety notices of this booklet as well as with the applicable safety regulations The successful and safe operation of this device i...

Страница 32: ... clean rooms The limit temperature range for storage of the relays or associated spare parts is 25 C to 55 C corresponding to 13 F to 131 F The relative humidity must be within limits such that neither condensation nor ice forms It is recommended to reduce the storage temperature to the range 10 C to 35 C 50 F to 95 F this prevents early ageing of the electrolytic capacitors which are contained in...

Страница 33: ...ule FO5 means that this is an optical 820 nm plug in module in the protection device which carries out a clock recovery from the transmitting clock of the communcation network For more details see SIPROTEC device manual The data transfer between the protection devices represents a point to point connection it is bit transparent and synchronous The communication converter supports simple commission...

Страница 34: ... 21 15 pole or 5 pole screw terminal G 703 Maximum line length for the connection between communication device communica tion converter for X 21 100 m 300 ft Maximum line length for the connection between communication device communica tion converter for G 703 1 300 m 900 ft Power supply unit with extended range for direct voltage 24 VDC to 250 VDC limit voltage 19 VDC to 300 VDC and alternating v...

Страница 35: ...ccurs synchro nously and completely bit transparent i e direct forwarding of the information without adding or filtering out information Figure 13 shows the hardware structure The interface type optionally X 21 or G 703 1 and the required transmission speed are set manually via jumpers Another jumper serves to switch over to Test mode for putting into operation and for service purposes Optical fib...

Страница 36: ...als of the G 703 1 interface must be applied to the 5 pole screw terminal G 703 one incoming and one outgoing pair of strands in each case The fifth screw terminal adjacent on the left S is for contacting the cable screen and is connected to the housing The G 703 1 signals are electrically isolated from the other electrical circuits Figure 13 Optical fibre The fibre optic interfaces serve to conne...

Страница 37: ...ed data are present and correspond to the standardized pulse mask Power supply The auxiliary voltage must be applied at the 2 pole screw terminal 24 250 VDC 115 250 VAC The permissible values and tolerances can be found in the Technical Data Page 47 The grounding connection on the right must be connected to the protective conductor PE Connection Instructions Screw terminals of the terminal blocks ...

Страница 38: ...ble for X 21 or G703 1 interface has to be at least of the type S UTP Screened Unshielded Twisted Pair An S UTP cable consists of a plastic sheath and a full length screen which contain the cores stranded in pairs The screen may be a copper braid or aluminium foil or both A type S FTP Screened Foil Twisted Pair cable may also be used This type of data cable has an additional metallic foil around t...

Страница 39: ...Between the communication converter and the X 21 interface of the communication device it is recommended to have short connenctions in order to avoid electrical interferences The communication converter should be installed near to the communication device DCE Please observe additional installation instructions Figure 17 Pin assignment of the 15 pole data cable on the device side X 21 T T C C R R I...

Страница 40: ...ptic links for the transmission and reception directions FO connector type ST connector Necessary fibre type Multimode FO cable G62 5 125 µm recommended Wavelength λ approx 820 nm Perm bending radii for indoor cables rmin 5 cm 2 in for outdoor cables rmin 20 cm 8 in Note Class 1 as defined by EN 60825 1 is met in the case of fibre type G62 5 125 µm FO 1 channel Warning Do not look directly into th...

Страница 41: ... where the interface connector is located The figure 17 shows the connection assignment on the DEE connection of the communi cation converter Insert the other end of the cable into the communication device you have selected It is essential to ensure that the wiring between the interfaces is correct When using the G 703 1 interface With a screwdriver connect the two core pair ends to the connection...

Страница 42: ...for interface X 21 X30 in position 2 3 for interface G 703 1 Selecting the transmission speed With the jumpers for X20 X22 X24 and X26 set the transmission speed necessary for communication see table 2 Only one slot can be occupied at any one time Note In the operating mode G 703 1 the jumper must be set to X20 since there is only one transmission rate for it 64 kBit s The transmission rate parame...

Страница 43: ... service tasks In this operating mode no signals pass through the communication converter Figure 20 The interfaces available are looped at the inputs so that parts of the entire communication path can be checked The DR relay is picked up in Test mode For more details about the procedure for putting a protection device into operation with the communication converter refer to the device manual of th...

Страница 44: ...ecure the cover of the converter with 6 screws and apply the auxiliary voltage again Display and operation There are four display and control elements on the KU XG These are one red two yellow and one green LED and one push button located on the top side of the housing LED1 Error The red LED Error directly signals the way in which the DR relay functions For the LED goes out certain conditions must...

Страница 45: ...unctional check of these signalling elements The LED states during putting into operation are shown in the following six steps for the structure see Figure 12 Here means any undefined LED state MAKE BREAK FLASHING Preconditions for putting into operation The jumper positions must correspond to the required operating mode baud rate in both KU XGs KU XG1 KU XG2 Step 1 KU XG1 is in the Power On state...

Страница 46: ...U XG2 Power On KU XG1 KU XG2 LED1 BREAK LED1 MAKE LED2 LED2 LED3 FLASHING LED3 LED4 MAKE LED4 MAKE Step 5 Apply the interface X 21 G 703 at KU XG2 KU XG1 KU XG2 LED1 BREAK LED1 BREAK LED2 LED2 FLASHING LED3 FLASHING LED3 LED4 MAKE LED4 MAKE Step 6 Connect the fibre optic cable at KU XG2 and start protection communication KU XG1 KU XG2 LED1 BREAK LED1 BREAK LED2 FLASHING LED2 FLASHING LED3 FLASHING...

Страница 47: ... circuit of the auxiliary voltage 50 ms AC voltage Alarm Relay DR Contact 1 changeover contact Switching capacity MAKE 1000 W 1000 VA BREAK 40 W 30 VA inductive Switching voltage 250 V Permissible current per contact 5 A continuous 30 A for 0 5 s Rated auxiliary voltage UH 24 V to 250 V Perm voltage range 19 V to 300 V Power input approx 3 5 W Nominal power supply alternating voltage UH 115 V to 2...

Страница 48: ...ssion distance 1 5 km 1 mile Interfaces to the communication device X 21 Connection 15 pin DSUB socket potential free Maximum transmission distance 100 m 512 kBit s 300 ft Transfer rate 64 kBit s or 128 kBit s or 256 kBit s or 512 kBit s adjustable Cable Please observe additional installation instructions G 703 1 Connection 5 pole screw terminal potential free Maximum transmission distance 300 m 9...

Страница 49: ...2 Product Standards EN 61000 6 2 Generic Standard VDE 0435 Part 301 DIN VDE 0435 110 High Frequency Test 2 5 kV Peak 1 MHz τ 15 µs IEC 60255 22 1 Class III and 400 Surges per s test duration 2 s VDE 0435 Part 303 Class III Ri 200 Ω Electrostatic Discharge 8 kV contact discharge IEC 60255 22 2 Class IV and 15 kV air discharge both polarities IEC 61000 4 2 Class IV 150 pF Ri 330 Ω Radiated disturban...

Страница 50: ...GE TBR14 3 ETS 300046 3 Sect 5 7 1 Communication interfaces common mode 2 kV 15 Ω 18 µF Line Conducted HF amplitude modulated 10 V 150 kHz to 80 MHz 80 AM 1 kHz IEC 61000 4 6 Class III Power System Frequency Magnetic Field IEC 61000 4 8 Class IV 30 A m continuous 300 A m for 3 s 50 Hz IEC 60255 6 0 5 mT 50 Hz Oscillatory Surge Withstand Capability 2 5 kV Peak Value 1 MHz τ 15 ms IEEE C37 90 1 400 ...

Страница 51: ...C 60255 21 and IEC 60068 2 Vibration Sinusoidal IEC 60255 21 1 Class 2 10 Hz to 60 Hz 0 075 mm Amplitude IEC 60068 2 6 60 Hz to 150 Hz 1 g acceleration frequency sweep rate 1 Octave min 20 cycles in 3 orthogonal axes Shock Half sine shaped IEC 60255 21 2 Class 1 acceleration 5 g duration 11 ms IEC 60068 2 27 3 shocks in each direction of 3 orthogonal axes Seismic Vibration Sinusoidal IEC 60255 21 ...

Страница 52: ... axes Climatic Stress Tests Temperatures IEC 60068 2 Recommended temperature during operation 5 C to 55 C or 23 F to 131 F Permissible temporary transient operating temperature 20 C to 70 C or 4 F to 158 F Type test acc IEC 60068 2 1 and 2 25 C to 85 C or 13 F to 185 F Test Bd for 16 h Limit temperatures during storage 40 C to 85 C or 40 F to 185 F Limit temperatures for operation 40 C to 85 C or ...

Страница 53: ...A00 English C53000 B1174 C134 7 53 Construction Housing Dimensions 188 mm 120 mm 55 mm W D H s Figures 21 and 22 Weight approx 0 8 kg Degree of protection according to EN 60529 Housing IP 41 Interface side IP 2x ...

Страница 54: ...mensions of the communication converter up to hardware version EE Mounting rails mounted on the wall are not included in the scope of delivery Unlocking 1 Minimum mounting rail length 2 The dimensioned drawing applies to the standard mounting rail IEC EN 60715 35 x 7 5 Dimensions in mm Cross recess screw ...

Страница 55: ... minor differences in the dimensions of devices from the hardware version FF as compared with devices up to the hardware version EE L 188 1 188 120 13 5 69 8 14 5 Mounting rails mounted on the wall are not included in the scope of delivery Cross recess screw Unlocking Dimensions in mm The dimensioned drawing applies to the standard mounting rail IEC EN 60715 35 x 7 5 1 Minimum mounting rail length...

Страница 56: ...English 7XV5662 0AA00 56 C53000 B1174 C134 7 ...

Страница 57: ...7XV5662 0AA00 C53000 B1174 C134 7 57 ...

Страница 58: ...h zugestanden Zuwiderhandlungen ver pflichten zu Schadenersatz Alle Rechte für den Fall der Patenterteilung oder GM Eintragung vorbehalten Copying this document and giving it to others and the use or communication of the contents thereof are forbidden without express authority Offenders are liable to the pay ment of damages All Rights are reserved in the event of the grant of a patent or registrat...

Отзывы: