Device Data
Supply Voltage
Auxiliary voltage – direct voltage
DC 24 V to 250 V (± 20 %)
Permissible ripple of the DC input voltage
15 %
Power consumption
8 W
Maximum inrush current at ≤ 110 V
< 15 A
Maximum inrush current at 220 V to 300 V
≤ 22 A
After 250 μs: < 5 A
Efficiency level
> 50 % at rated load
Auxiliary voltage – alternating voltage
AC 60 V to 230 V (± 20 %) at 45 Hz to 65 Hz
Permissible higher harmonics
2 kHz
Maximum inrush current at ≤ 115 V
< 15 A
Maximum inrush current at 230 V
≤ 22 A
After 250 μs: < 5 A
Power consumption
18 VA
Power-failure backup
Min. 50 ms at rated load
Output-voltage status display
1 green LED to display the operating state
Fault-Signaling Connection (Relay)
Relay
MSR relay, 1 break contact, isolated; 2-pole terminal
Maximum contact voltage with a resistive load
AC 240 V
Maximum switching current
5 A
Maximum switching power
AC 2000 VA
Permissible current for contacts
5 A
Test voltage
V
RMS
= 3.51 kV
Fuses
Not replaceable
T 2.0 A
Replaceable
T 1.6 A at AC 250 V or DC 300 V
Safety
As per DIN EN 61010 Part 1, overvoltage category
III
Degree of pollution
2
Fire-resistance rating as per UL 94
V0
5.1
Technical Data
5.1 Device Data
42
Accessories, Mini Star Coupler, Manual
C53000-G9050-C595-1, Edition 05.2020
Содержание 7XV5450-0BA00/BB
Страница 20: ...20 Zubehör Mini Sternkoppler Handbuch C53000 G9050 C595 1 Ausgabe 05 2020 ...
Страница 32: ...32 Zubehör Mini Sternkoppler Handbuch C53000 G9050 C595 1 Ausgabe 05 2020 ...
Страница 50: ...50 Zubehör Mini Sternkoppler Handbuch C53000 G9050 C595 1 Ausgabe 05 2020 ...
Страница 56: ...6 Accessories Mini Star Coupler Manual C53000 G9050 C595 1 Edition 05 2020 ...
Страница 70: ...20 Accessories Mini Star Coupler Manual C53000 G9050 C595 1 Edition 05 2020 ...
Страница 82: ...32 Accessories Mini Star Coupler Manual C53000 G9050 C595 1 Edition 05 2020 ...
Страница 100: ...50 Accessories Mini Star Coupler Manual C53000 G9050 C595 1 Edition 05 2020 ...