7SR224 Argus Performance Specification
1.2
Energising Quantities
1.2.1 Auxiliary Power Supply
Nominal
Operating
Range
V
AUX
30, 48, 110, 220 VDC
24 to 290 VDC
1.2.1.1
Burden
Attribute Value
Quiescent (typical)
6.0 W
30V DC
Quiescent (back light) 7.0 W
Quiescent (typical)
5.5W
48V DC
Quiescent (back light) 6.5W
Quiescent (typical)
6.5W
110V DC
Quiescent (back light) 7.5W
Quiescent (typical)
7.5W
220V DC
Quiescent (back light) 8.5W
1.2.2
AC Current
Nominal
Measuring
Range
In
1, 5 A Phase and earth
80 x
In
fn
50, 60Hz
47 to 62Hz
Note. 1 A and 5 A nominal inputs are user selectable on each model.
1.2.2.1
Burden
Value - Phase and Earth
Attribute
1A 5A
AC Burden
≤
0.1 VA
≤
0.3 VA
1.2.2.2
Thermal Withstand
Overload Current
Phase and Earth
Overload Period
1A 5A
Continuous 3.0
xIn
10 minutes
3.5
xIn
5 minutes
4.0
xIn
3 minutes
5.0
xIn
2 minutes
6.0
xIn
3 seconds
57.7A
202A
2 seconds
70.7A
247A
1 second
100A
350A
1 cycle
700A
2500A