7SR224 Argus Description of Operation
6.6
Operating Mode
The relay has three operating modes, Local, Remote and Out of Service. The following table identifies the
functions operation in each mode.
The modes can be selected by the following methods:
SYSTEM CONFIG>
RELAY MODE
setting, a Binary Input or Command
OPERATION
REMOTE MODE
LOCAL MODE
SERVICE MODE
Control
Rear Ports
Enabled
Disabled
Disabled
Fascia (Control Mode)
Disabled
Enabled
Disabled
USB
Disabled Enabled Disabled
Binary Inputs
Setting Option Setting
Option
Enabled
Binary Outputs
Enabled
Enabled
Disabled
Reporting
Spontaneous
IEC Enabled
Enabled
Disabled
DNP Enabled
Enabled
Disabled
General
Interogation
IEC Enabled
Enabled
Disabled
DNP Enabled
Enabled
Disabled
MODBUS
Enabled Enabled Enabled
Changing of Settings
Rear
Ports
Enabled Disabled Enabled
Fascia
Enabled Enabled Enabled
USB Disabled
Enabled
Enabled
Historical Information
Waveform
Records
Enabled Enabled Enabled
Event
Records
Enabled Enabled Enabled
Fault
Information
Enabled Enabled Enabled
Setting
Information
Enabled Enabled Enabled
Table 6-1
Operation Mode
6.7
Control Mode
This mode provides convenient access to commonly used relay control and test functions. When any of the items
listed below are selected control is initiated by pressing the ENTER key. The user is prompted to confirm the
action, again by pressing the ENTER key, before the command is executed.
Control Mode commands could be password protected using the Control Password function – see section 6.8.
Commands available in the Control Mode are:
Open CB
Close CB
79 In/Out
79 Trip and Reclose
79 Trip & Lockout
Hotline Work In/Out
E/F In/Out
SEF In/Out
Instantaneous Protection In/Out
Battery Test Required
©2010 Siemens Protection Devices Limited
Chapter 1 Page 68 of 70