7SR224 Argus Description of Operation
Minimum Polarising Voltage
The
67 Minimum Voltage
setting defines the minimum polarising voltage level. Where the measured polarising
voltage is below this level no directional output is given and operation of protection elements set as directional will
be inhibited. This prevents mal-operation under fuse failure/MCB tripped conditions where noise voltages can be
present.
Figure 3.1-1 Logic Diagram: Directional Overcurrent Element (67)
©2010 Siemens Protection Devices Limited
Chapter 1 Page 18 of 70