7SR224 Argus Data Comms
©2010 Siemens Protection Devices Limited
Chapter 4 Page 6 of 76
Setting name
Range
Default
Setting
Notes
I101 Background
Period
Off, 1 ..1500 minutes
Off
As Required
Period device will
generate background
data. Set to Off to disable
generating of background
data. Only data points
with the background flag
set will be generated in
the background.
2.1.3 USB Interface
The USB communication port is connected using a standard USB cable with a type B connection to the relay and
type A to the PC.
The PC will require a suitable USB driver to be installed, this will be carried out automatically when the Reydisp
software is installed. When the Reydisp software is running with the USB cable connected to a device an
additional connection is shown. Connections to these devices are not shown when they are not connected.
The USB communication interface on the relay is labelled Com 2 and its associated settings are located in the
Data communications menu. When connecting to Reydisp using this connection the default settings can be used
without the need to first change any settings, otherwise the Com 2 port must be set to IEC60870-5-103 (the relay
address and baud rate do not need to be set).
Setting name
Range
Default
Setting
Notes
Station Address
1 … 254
0
1-254
An address between 1 and
254 must be given to identify
the relay
COM2-USB Protocol
OFF, IEC60870-5-103,
DNP3.0 or IEC60870-5-
101, MODBUS-RTU,
ASCII
IEC60870-5-
103
IEC60870-
5-103
Reydisp software uses
IEC60870-5-103 to
communicate.
COM2 Mode
Local, Remote, Local Or
Remote
Local Local Selects port mode
Local
Engineer
Access
USB Type A
USB Data Cable
USB Type A
socket on PC
USB Type B
Figure 2-1
Communication to Front USB Port