
7SR224 Argus Performance Specification
2.11 51SEF Time Delayed Sensitive Earth Fault
2.11.1 Reference
Parameter
Value
Is
Setting 0.005,
0.006
…0.100, 0.105… 1.0
xIn
char
Characteristic setting
IEC-NI, -VI, -EI, -LTI;
ANSI-MI, -VI, -EI; DTL
Manufacturer specific curves
See ‘Performance Specification Appendix 1’
Tm
Time multiplier
1.0
t
d
Delay setting
0.00…20.00 s
t
res
Reset setting
DECAYING, 0, 1…60 s
IDMTL
2 to 20 x
Is
I
Applied current (for
operate time)
DTL
5
x
Is
2.11.2 Operate and Reset Level
Attribute
Value
I
op
Operate level
105 %
Is
,
±
4 % or
±
1% In
Reset level
≥
95 %
I
op
±
4 % or
±
1% In
Repeatability
±
1 %
-10 °C to +55 °C
≤
5 %
Variation
f
nom
- 3 Hz
to
f
nom
+ 2 Hz
harmonics to
f
cutoff
≤
5 %
©2010 Siemens Protection Devices Limited
Chapter 3 Page 33 of 49