7SR224 Argus Performance Specification
2.8
50SEF Instantaneous Sensitive Earth Fault
2.8.1 Reference
Parameter
Value
Is
Setting
0.005, 0.006 …0.1, 0.105 .. 5 x
In
t
d
Delay setting
0.00
, 0.01… 20.0, 20.1 .. 100.0, 101.…1000, 1010 …
10000 , 10100 … 14400
I
Applied current (for operate time)
5 x
Is
2.8.2 Operate and Reset Level
Attribute
Value
I
op
Operate level
100 %
Is
,
±
5 % or
±
1% In
Reset level
≥
95 %
I
op
±
5 % or
±
1% In
Repeatability
±
1 %
Transient overreach
(X/R
≤
100)
≤
-5 %
-10 °C to +55 °C
≤
5 %
Variation
f
nom
- 3 Hz to
f
nom
+ 2 Hz
harmonics to
f
cutoff
≤
5 %
2.8.3 Operate and Reset Time
Attribute
Value
0 to 2 x
Is
: 35 ms,
±
10ms
t
basic
Element basic
operate time
0 to 5 xI
s
: 25 ms,
±
10ms
t
op
Operate time following delay
t
basic
+
t
d
,
±
1 % or
±
10ms
Repeatability
±
1 % or
±
10ms
Overshoot time
< 40 ms
Disengaging time
< 50 ms
Variation
f
nom
- 3 Hz to
f
nom
+ 2 Hz
≤
5 %
©2010 Siemens Protection Devices Limited
Chapter 3 Page 25 of 49