Table 1.4-1
7SR18 Ordering Options
7
S
R
1
8
1
-
-
0
A
0
Protection Product Family
Differential Protection
8
Case size
E6
2)
1
I/O and Fascia
3 Binary Inputs, 5 Binary Outputs, 18 LEDs
1
C
2
C
6 Binary Inputs, 8 Binary Outputs, 18 LEDs
3
6 Binary Inputs, 8 Binary Outputs, 10 LEDs + (6 keys each with LED)
4
Measuring input
4 CTs (1 A or 5 A)
1
4 CTs (1 A or 5 A), 3 VTs (40 V to 160 V)
2
C
Auxiliary voltage
24 V DC to 250 V DC, 100 V AC to 230 V AC, binary input threshold 19 V DC
M
24 V DC to 250 V DC, 100 V AC to 230 V AC, binary input threshold 88 V DC
N
Protection Signalling Channel
Optical fibre link (820 nm) (ST connection) 2 km
1)
B
1
Optical fibre link (1300 nm) (LC connection) 40 km
1)
C
Data Communication Interface
USB front port, RS485 (Terminal block) rear port
1
2
USB front port, RS485 (Terminal block) rear port, Electrical Ethernet RJ45 (x2) rear port
7
7
USB front port, RS485 (Terminal block) rear port, Optical Ethernet Duplex (x2) rear port
8
7
Protocol
IEC 60870-5-103 and Modbus RTU and DNP 3.0 (user selectable)
2
IEC 60870-5-103 and Modbus RTU and DNP 3.0 (user selectable) and IEC61850
7
Spare
0
Protection Function Packages
Standard version
C
87L
3-Phase differential (with variable settings)
87HS
3-Phase Differential High Set
85
Inter-Trip
50
Instantaneous phase fault overcurrent
50G/50N
Instantaneous earth fault
51
Time delayed phase fault overcurrent
51G/51N
Time delayed earth fault
50LC
Line Check
37
Undercurrent
46NPS
Negative phase sequence overcurrent
49
Thermal overload
50BF
Circuit breaker fail
46BC
Broken conductor/load unbalance
60CTS-I
CT Supervision
74T&C
Trip & Close circuit supervision
51c
Cold load pickup
81HBL2
Inrush Detector
Programmable Logic
For variants with 3 x VT inputs as above plus
51V
Voltage Controlled Overcurrent
60CTS
CT Supervision
60 VTS
VT supervision
67/50, 67/51
Directional Overcurrent
67 G/N
Directional Earth Fault
Version C - plus
D
79
Autoreclose
Additional Functionality
No additional functionality
A
Spare
0
3 Binary Inputs, 5 Binary Outputs, 10 LEDs + (6 keys each with LED)
1)
Refer to Technical Manual
2)
Standard Version Cover - No Push Buttons
Содержание 7SR18 Solkor
Страница 1: ...Energy Management 7SR18 Solkor Line Differential Relay Reyrolle Protection Devices ...
Страница 2: ...Siemens Protection Devices Limited 2 ...
Страница 93: ...7SR18 Configuration Guide Unrestricted Page 12 of 12 2015 Siemens Protection Devices Limited ...
Страница 161: ...7SR18 Performance Specification Unrestricted Page 44 of 44 2018 Siemens Protection Devices Limited ...
Страница 179: ...7SR18 Solkor Settings Guide Unrestricted Page 4 of 44 2016 Siemens Protection Devices Limited Typical Menu Structure ...
Страница 221: ...7SR181 Solkor Technical Manual Chapter 4 Page 2 of 80 2016 Siemens Protection Devices Limited ...
Страница 225: ...7SR181 Solkor Technical Manual Chapter 4 Page 6 of 80 2016 Siemens Protection Devices Limited ...
Страница 289: ...7SR181 Solkor Technical Manual Chapter 4 Page 70 of 80 2016 Siemens Protection Devices Limited ...
Страница 291: ...7SR181 Solkor Technical Manual Chapter 4 Page 72 of 80 2016 Siemens Protection Devices Limited ...
Страница 293: ...7SR181 Solkor Technical Manual Chapter 4 Page 74 of 80 2016 Siemens Protection Devices Limited ...
Страница 353: ...7SR18 Commissioning Maintenance Guide Unrestricted Page 54 of 54 2018 Siemens Protection Devices Limited ...