Chapter 4 - 7SR157 · Data Communications Definitions
© 2016 Siemens Protection Devices Limited
Chapter 4 - Page 45 of 58
The default counter event buffer size is set 30. The counter event mode is set to Most Recent, only most recent event
for each point is stored.
Counters are by default returned in a class zero interrogation.
Note, not all points listed here apply to all builds of devices.
Counters
Static (Steady-State) Object Number: 20
Change Event Object Number: 22
Static Variation reported when variation 0 requested: 1 (32-Bit Counter with Flag)
or 2 (16-Bit Counter with Flag)
or 5 (32-Bit Counter w/o Flag)
or 6 (16-Bit Counter w/o Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Counter Event with Flag)
or 2 (16-Bit Counter Event with Flag)
or 5 (32-Bit Counter Event with Flag and Time)
or 6 (16-Bit Counter Event with Flag and Time)
Frozen Counters
Static (Steady-State) Object Number: 21
Change Event Object Number: 23
Static Variation reported when variation 0 requested: 1 (32-Bit Frozen Counter with Flag)
or 2 (16-Bit Frozen Counter with Flag)
or 5 (32-Bit Frozen Counter with Flag and Time)
or 6 (16-Bit Frozen Counter with Flag and Time)
or 9 (32-Bit Frozen Counter w/o Flag)
or 10 (16-Bit Frozen Counter w/o Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Frozen Counter Event with Flag)
or 2 (16-Bit Frozen Counter Event with Flag)
or 5 (32-Bit Frozen Counter Event with Flag and Time)
or 6 (16-Bit Frozen Counter Event with Flag and Time)
Counter
Frozen Counter
Point
Index
Description
Default
Change
Event
Assigned
Class
(1, 2, 3
or none)
Default
Variation
Static
Object 20
Default
Variation
Event
Object 22
Deadband
Is Resettable
IsFreezable
Default
Change
Event
Assigned
Class
(1, 2, 3
or none)
Default
Variation
Static
Object 21
Default
Variation
Event
Object 23
0 Waveform Records
0,3
5
1
1
✔
0,2
9
1
1 Fault Records
0,3
5
1
1
✔
0,2
9
1
2 Event Records
0,3
5
1
1
✔
0,2
9
1
3 Data Log Records
0,3
5
1
1
✔
0,2
9
1
7 Active Setting Group
0,3
5
1
1
✔
0,2
9
1
21 E1 Counter
0,3
5
1
1
✔
0,2
9
1
22 E2 Counter
0,3
5
1
1
✔
0,2
9
1
23 E3 Counter
0,3
5
1
1
✔
0,2
9
1
24 E4 Counter
0,3
5
1
1
✔
0,2
9
1
5.3.5 Analog Inputs
The following table lists Analog Inputs (Object 30). It is important to note that 16-bit and 32-bit variations of Analog
Inputs, Analog Output Control Blocks, and Analog Output Statuses are transmitted through DNP as signed numbers.
The “Default Deadband,” and the “Default Change Event Assigned Class” columns are used to represent the absolute
amount by which the point must change before an Analog change event will be generated, and once generated in
which class poll (1, 2, 3, or none) will the change event be reported.
The default analog input event buffer size is set 30. The analog input event mode is set to Most Recent, only most
recent event for each point is stored.
Содержание 7SR157 Argus
Страница 1: ...Energy Management 7SR157 Argus Check and System Synchronising Relay Reyrolle Protection Devices ...
Страница 2: ......
Страница 4: ...7SR157 Contents ...
Страница 58: ...7SR158 Technical Manual Chapter 3 Page 2 of 18 2022 Siemens Protection Devices Limited ...
Страница 76: ...7SR157 Technical Manual Chapter 4 Page 2 of 58 2016 Siemens Protection Devices Limited ...
Страница 80: ...7SR157 Technical Manual Chapter 4 Page 6 of 58 2016 Siemens Protection Devices Limited ...
Страница 92: ...7SR157 Technical Manual Chapter 4 Page 18 of 58 2016 Siemens Protection Devices Limited ...
Страница 122: ...7SR157 Technical Manual Chapter 4 Page 48 of 58 2016 Siemens Protection Devices Limited ...
Страница 124: ...7SR157 Technical Manual Chapter 4 Page 50 of 58 2016 Siemens Protection Devices Limited ...
Страница 126: ...7SR157 Technical Manual Chapter 4 Page 52 of 58 2016 Siemens Protection Devices Limited ...
Страница 150: ...7SR157 Technical Manual Chapter 5 Page 18 of 18 2018 Siemens Protection Devices Limited ...
Страница 161: ...Chapter 6 7SR157 Commissioning and Maintenance Guide Chapter 6 Page 11 of 14 2016 Siemens Protection Devices Limited ...
Страница 179: ...Siemens Protection Devices 1 ...