Binary Input Points
Static (Steady-State) Object Number: 1 (Packed Format)
Change Event Object Number: 1 (w/o Time)
Static Variation reported when variation 0 requested: 1 (Binary Input w/o status)
or 2 (Binary Input with status)
Change Event Variation reported when variation 0 requested: 1 (Binary Input Change w/o Time)
or 2 (Binary Input Change with Absolute Time)
or 3 (Binary Input Change with Relative Time)
Point
Index
Description
Default Change Event
Assigned Class
(1, 2, 3 or none)
Default Variation
Static Object 1
Default Variation
Event Object 2
962 Restart Inhibit
0,2
2
2
963 49 Restart Inhibit
0,2
2
2
964 Motor Fail To Run
0,2
2
2
965 66 Starts Exceeded
0,2
2
2
966 Motor Starting
0,2
2
2
967 Motor Running
0,2
2
2
968 Motor Stopped
0,2
2
2
969 49 Load Alarm
0,2
2
2
970 49 Overload Alarm
0,2
2
2
971 46 PH REV
0,2
2
2
972 Close CB Failed
0,2
2
2
973 Open CB Failed
0,2
2
2
5.3.2 Double Bit Input Points
The default double bit input event buffer size is set to allow 100 events.
Double bit inputs are by default returned in a class zero interrogation.
Note, not all points listed here apply to all builds of devices.
Double Bit Input Points
Static (Steady-State) Object Number: 3
Change Event Object Number: 4
Static Variation reported when variation 0 requested: 1 (Double Bit Input w/o status)
or 2 (Double Bit Input with status)
Change Event Variation reported when variation 0 requested: 1 (Double Bit Input Change w/o Time)
or 2 (Double Bit Input Change with Absolute Time)
or 3 (Double Bit Input Change with Relative Time)
Point
Index
Description
Default Change Event
Assigned Class
(1, 2, 3 or none)
Default Variation
Static Object 3
Default Variation
Event Object 4
0 CB 1
0,2
1
3
10 User DP Command 1
0,2
1
3
11 User DP Command 2
0,2
1
3
12 User DP Command 3
0,2
1
3
13 User DP Command 4
0,2
1
3
14 User DP Command 5
0,2
1
3
15 User DP Command 6
0,2
1
3
16 User DP Command 7
0,2
1
3
17 User DP Command 8
0,2
1
3
5.3.3 Binary Output Status Points and Control Relay Output Blocks
Содержание 7SR105 Rho
Страница 1: ...Answers for energy 7SR105 Rho User Manual Motor Protection Relay Reyrolle Protection Devices ...
Страница 2: ...Siemens Protection Devices 2 ...
Страница 95: ...7SR105 Rho Technical Manual Chapter 4 Page 2 of 70 2018 Siemens Protection Devices ...
Страница 99: ...7SR105 Rho Technical Manual Chapter 4 Page 6 of 70 2018 Siemens Protection Devices ...
Страница 127: ...7SR105 Rho Technical Manual Chapter 4 Page 34 of 70 2018 Siemens Protection Devices ...
Страница 153: ...7SR105 Rho Technical Manual Chapter 4 Page 60 of 70 2018 Siemens Protection Devices ...
Страница 155: ...7SR105 Rho Technical Manual Chapter 4 Page 62 of 70 2018 Siemens Protection Devices ...
Страница 157: ...7SR105 Rho Technical Manual Chapter 4 Page 64 of 70 2018 Siemens Protection Devices ...