7SR105 Rho Description of Operation
©2018 Siemens Protection Devices Chapter 1 Page 55 of 57
6.5 Operating Mode
The relay has three operating modes - Local, Remote, and Out of Service. The following table identifies the
functions operation in each mode.
The modes can be selected by the following methods:
SYSTEM CONFIG > OPERATING
MODE
setting, a Binary Input or Command
Table 6-1
Operation Mode
OPERATION
REMOTE MODE
LOCAL MODE
SERVICE MODE
Control
Rear Ports
Enabled
Disabled
Disabled
Fascia (Control Mode)
Disabled
Enabled
Disabled
USB
Disabled
Enabled
Disabled
Binary Inputs
Setting Option
Setting Option
Enabled
Binary Outputs
Enabled
Enabled
Disabled
Reporting
Spontaneous
IEC
Enabled
Enabled
Disabled
DNP
Enabled
Enabled
Disabled
General Interrogation
IEC
Enabled
Enabled
Disabled
DNP
Enabled
Enabled
Disabled
MODBUS
Enabled
Enabled
Enabled
Changing of Settings
Rear Ports
Enabled
Disabled
Enabled
Fascia
Enabled
Enabled
Enabled
USB
Disabled
Enabled
Enabled
Historical Information
Waveform Records
Enabled
Enabled
Enabled
Event Records
Enabled
Enabled
Enabled
Fault Information
Enabled
Enabled
Enabled
Setting Information
Enabled
Enabled
Enabled
6.6 Control Mode
This mode provides convenient access to the relay control functions listed below. When any of the items listed
below are selected control is initiated by pressing the ENTER key. The user is prompted to confirm the action,
again by pressing the ENTER key, before the command is executed.
CB Control
E/F In
Set Local or Remote
Set Remote
Set Local
Set Service
Note that the CB must be in a Closed state before an Stop command will be accepted. And that the CB must be in
an Open state before a Start command will be accepted.
Note also that switching a protection function IN / OUT via the Control Menu will not change that function’s
ENABLED / DISABLED setting. The Control Menu selection will over-ride the setting, however.
Control Mode commands are password protected using the Control Password function, see
Содержание 7SR105 Rho
Страница 1: ...Answers for energy 7SR105 Rho User Manual Motor Protection Relay Reyrolle Protection Devices ...
Страница 2: ...Siemens Protection Devices 2 ...
Страница 95: ...7SR105 Rho Technical Manual Chapter 4 Page 2 of 70 2018 Siemens Protection Devices ...
Страница 99: ...7SR105 Rho Technical Manual Chapter 4 Page 6 of 70 2018 Siemens Protection Devices ...
Страница 127: ...7SR105 Rho Technical Manual Chapter 4 Page 34 of 70 2018 Siemens Protection Devices ...
Страница 153: ...7SR105 Rho Technical Manual Chapter 4 Page 60 of 70 2018 Siemens Protection Devices ...
Страница 155: ...7SR105 Rho Technical Manual Chapter 4 Page 62 of 70 2018 Siemens Protection Devices ...
Страница 157: ...7SR105 Rho Technical Manual Chapter 4 Page 64 of 70 2018 Siemens Protection Devices ...