7SR105 Rho Description of Operation
©2018 Siemens Protection Devices Chapter 1 Page 53 of 57
6.3 Data Storage
6.3.1 General
The relay stores three types of data- relay event records, analogue/digital waveform records, and fault records.
Data records are backed up in non-volatile memory and are permanently stored even in the event of loss of
auxiliary supply voltage. The data storage menu contains the settings for the Demand, Waveform, and Fault
storage features.
6.3.2 Demand
Maximum, minimum and mean values of line currents, voltages and power (where applicable) are available as
instruments which can be read in the relay INSTRUMENTS MENU or via Reydisp.
The
Gn Demand Window
setting defines the maximum period of time over which the demand values are valid. A
new set of demand values is established after expiry of the set time.
The
Gn Demand Window Type
can be set to
FIXED
or
PEAK
or
ROLLING
.
When set to
FIXED
the maximum, minimum and mean values demand statistics are calculated over
fixed Window duration. At the end of each window the internal statistics
are reset and a new window is started.
When set to
PEAK
the maximum and minimum values since the feature was reset are recorded.
When set to
ROLLING
the maximum, minimum and mean values demand statistics are calculated over
a moving Window duration. The internal statistics
are updated when the window advances every
Updated Period
.
The statistics can be reset from a binary input or communication command, after a reset the update period and
window are immediately restarted.
6.3.3 Event Records
The event recorder feature allows the time tagging of any change of state (Event) in the relay. As an event
occurs, the actual event condition is logged as a record along with a time and date stamp to a resolution of 1 ms.
There is capacity for a maximum of 1000 event records that can be stored in the relay and when the event buffer
is full any new record will over-write the oldest. Stored events can be erased using the
DATA STORAGE
>
Clear
Events
setting or from Reydisp.
The following events are logged:
•
Change of state of Binary outputs
•
Change of state of Binary inputs
•
Change of settings and settings group
•
Change of state of any of the control functions of the relay
•
Protection element operation
All events can be uploaded over the data communications channel(s) and can be displayed in the ‘Reydisp’
package in chronological order allowing the sequence of events to be viewed. Events can be selected to be made
available spontaneously to an IEC 60870-5-103, Modbus RTU, or DNP 3.0 compliant control system. The function
number and event number can also be changed. The events are selected and edited using the Reydisp software
tool.
6.3.4 Waveform Records
Relay waveform storage can be triggered either by user selecting the relay operations from the relay fascia from a
suitably programmed binary input or via the data communications channel(s). The stored analogue and digital
waveforms illustrates the system and relay conditions at the time of trigger. An output is provided to indicate
when a new record has been stored.
A waveform can also be stored from the fascia using the
DATA STORAGE/Waveform Storage >
Trigger
Waveform
setting.
In total, the relay provides 15 s of waveform storage; this is user selectable to 15 Rec x 1 Sec,
7 Rec x 2 Sec, 3 Rec x 5 Sec, 1 Rec x 15 Sec records. When the waveform recorder buffer is full any new
waveform record will over-write the oldest. The most recent record is Waveform 1.
As well as defining the stored waveform record duration, the user can select the percentage of the waveform
storage prior to triggering.
Содержание 7SR105 Rho
Страница 1: ...Answers for energy 7SR105 Rho User Manual Motor Protection Relay Reyrolle Protection Devices ...
Страница 2: ...Siemens Protection Devices 2 ...
Страница 95: ...7SR105 Rho Technical Manual Chapter 4 Page 2 of 70 2018 Siemens Protection Devices ...
Страница 99: ...7SR105 Rho Technical Manual Chapter 4 Page 6 of 70 2018 Siemens Protection Devices ...
Страница 127: ...7SR105 Rho Technical Manual Chapter 4 Page 34 of 70 2018 Siemens Protection Devices ...
Страница 153: ...7SR105 Rho Technical Manual Chapter 4 Page 60 of 70 2018 Siemens Protection Devices ...
Страница 155: ...7SR105 Rho Technical Manual Chapter 4 Page 62 of 70 2018 Siemens Protection Devices ...
Страница 157: ...7SR105 Rho Technical Manual Chapter 4 Page 64 of 70 2018 Siemens Protection Devices ...