7SR105 Rho Technical Manual
Chapter 4 - Page 44 of 70
© 2018 Siemens Protection Devices
5.3 Point List
The tables below identify all the default data points provided by the implementation of the Triangle MicroWorks, Inc.
DNP 3.0 Slave Source Code Library.
This protocol can be set to use any or all of the relays hardware interfaces (USB and RS485) where fitted. The relay
can communicate simultaneously on all ports regardless of protocol used.
The Station Address of the port being used must be set to a suitable address within the range 0 - 65534 to enable
communication. This can be set by the Communications Menu : COM n-xxxxx Station Address setting.
The information shown below is the default configuration. This can be modified using the Communications
Configuration Editor tool, refer
5.3.1 Binary Input Points
The default binary input event buffer size is set to allow 100 events.
Binary inputs are by default returned in a class zero interrogation.
Note, not all points listed here apply to all builds of devices.
Binary Input Points
Static (Steady-State) Object Number: 1 (Packed Format)
Change Event Object Number: 1 (w/o Time)
Static Variation reported when variation 0 requested: 1 (Binary Input w/o status)
or 2 (Binary Input with status)
Change Event Variation reported when variation 0 requested: 1 (Binary Input Change w/o Time)
or 2 (Binary Input Change with Absolute Time)
or 3 (Binary Input Change with Relative Time)
Point
Index
Description
Default Change Event
Assigned Class
(1, 2, 3 or none)
Default Variation
Static Object 1
Default Variation
Event Object 2
1 Binary Input 1
0,2
2
2
2 Binary Input 2
0,2
2
2
3 Binary Input 3
0,2
2
2
4 Binary Input 4
0,2
2
2
5 Binary Input 5
0,2
2
2
6 Binary Input 6
0,2
2
2
35 Remote Mode
0,2
2
2
36 Out Of Service Mode
0,2
2
2
37 Local Mode
0,2
2
2
38 Local & Remote
0,2
2
2
40 General Trip
0,2
2
2
41 Trip Circuit Fail
0,2
2
2
42 Start/Pick-up L1
0,2
2
2
43 Start/Pick-up L2
0,2
2
2
44 Start/Pick-up L3
0,2
2
2
45 General Start/Pick-up
0,2
2
2
49 Start/Pick-up N
0,2
2
2
52 51-1
0,2
2
2
53 50-1
0,2
2
2
54 51N-1
0,2
2
2
55 50N-1
0,2
2
2
56 51G-1
0,2
2
2
57 50G-1
0,2
2
2
Содержание 7SR105 Rho
Страница 1: ...Answers for energy 7SR105 Rho User Manual Motor Protection Relay Reyrolle Protection Devices ...
Страница 2: ...Siemens Protection Devices 2 ...
Страница 95: ...7SR105 Rho Technical Manual Chapter 4 Page 2 of 70 2018 Siemens Protection Devices ...
Страница 99: ...7SR105 Rho Technical Manual Chapter 4 Page 6 of 70 2018 Siemens Protection Devices ...
Страница 127: ...7SR105 Rho Technical Manual Chapter 4 Page 34 of 70 2018 Siemens Protection Devices ...
Страница 153: ...7SR105 Rho Technical Manual Chapter 4 Page 60 of 70 2018 Siemens Protection Devices ...
Страница 155: ...7SR105 Rho Technical Manual Chapter 4 Page 62 of 70 2018 Siemens Protection Devices ...
Страница 157: ...7SR105 Rho Technical Manual Chapter 4 Page 64 of 70 2018 Siemens Protection Devices ...