7SR10 Description of Operation
©2018 Siemens Protection Devices Limited Chapter 1 Page 43 of 77
IL 4 (I
G
)
Inhibit 37G- n
37G- n Setting
c
&
37G - n
Enabled
Disabled
<
37G- n Delay
37G-n
General Pickup
Figure 3-20 Logic Diagram: Earth Current Inputs Undercurrent Detector (37G)
(ISEF)
37 SEF- n
Inhibit 37SEF-n
37 SEF- n Setting
c
&
37 SEF-n
Enabled
Disabled
<
37 SEF - n Delay
IL4
General Pickup
Figure 3-21 Logic Diagram: Sensitive Earth Current Inputs Undercurrent Detector (37SEF)
3.4.8 Current Protection: Thermal Overload (49)
The relay provides a thermal overload suitable for the protection of static plant. Phase segregated elements are
provided. The temperature of the protected equipment is not measured directly. Instead, thermal overload
conditions are calculated using the measure True RMS current.
Should the current rise above the
49 Overload Setting
for a defined time an output signal will be initiated. The
operating time is a function of thermal time constant
49 Time Constant
and previous current levels.
Operate Time (t):-
(
)
×
−
−
×
=
2
B
2
2
P
2
I
k
I
I
I
ln
t
τ
Where
T = Time in minutes
τ
=
49 Time Constant
setting (minutes)
In = Log Natural
I = measured current
I
P
= Previous steady state current level
k = Constant (recommended value, k = 1.05)
I
B
= Basic current, typically the same as In
k.I
B
=
49 Overload
Setting (I
θ
)
Additionally, an alarm can be given if the thermal state of the system exceeds a specified percentage of the
protected equipment’s thermal capacity
49 Capacity Alarm
setting.
For the heating curve:
100%
)
e
(1
I
I
θ
τ
t
2
θ
2
×
−
⋅
=
−
Where:
θ
= thermal state at time t
I = measured thermal current
I
θ
=
49 Overload
setting (or k.I
B
)
The final steady state thermal condition can be predicted for any steady state value of input current where t >
τ
,
100%
I
I
θ
2
θ
2
F
×
=
Where:
θ
F
= final thermal state before disconnection of device
Содержание 7SR10 Argus Series
Страница 1: ...7SR10 Argus Overcurrent Relay Reyrolle Protection Devices ...
Страница 2: ...Siemens Protection Devices Limited 2 ...
Страница 152: ...7SR10 Technical Manual Chapter 4 Page 2 of 78 2018 Siemens Protection Devices ...
Страница 156: ...7SR10 Technical Manual Chapter 4 Page 6 of 78 2018 Siemens Protection Devices ...
Страница 188: ...7SR10 Technical Manual Chapter 4 Page 38 of 78 2018 Siemens Protection Devices ...
Страница 216: ...7SR10 Technical Manual Chapter 4 Page 66 of 78 2018 Siemens Protection Devices ...
Страница 218: ...7SR10 Technical Manual Chapter 4 Page 68 of 78 2018 Siemens Protection Devices ...
Страница 220: ...7SR10 Technical Manual Chapter 4 Page 70 of 78 2018 Siemens Protection Devices ...
Страница 222: ...7SR10 Technical Manual Chapter 4 Page 72 of 78 2018 Siemens Protection Devices ...