No.
Information
Data Class
(Type)
Type
_:8161:67
Inverse-T 1:Dyn.set. BI active
SPS
O
_:8161:68
Inverse-T 1:Dyn. set. blks. pickup
SPS
O
_:8161:59
Inverse-T 1:Disk emulation running
SPS
O
_:8161:55
Inverse-T 1:Pickup
ACD
O
_:8161:300
Inverse-T 1:Direction
ACD
O
_:8161:56
Inverse-T 1:Operate delay expired
ACT
O
_:8161:57
Inverse-T 1:Operate
ACT
O
Stage with User-Defined Characteristic Curve
Description
The structure of this stage is identical to that of the advanced stage with directional inverse-time characteristic
curve (
). The only difference is that you can define the characteristic curve as desired.
User-Defined Characteristic Curve
With the directional, user-defined characteristic curve, you can define the operate curve point by point using
up to 30 value pairs of current and time. The device uses linear interpolation to calculate the characteristic
curve from these values. You can also define a dropout characteristic curve if you wish.
Pickup and Dropout Behaviors with User-Defined Characteristic Curve
When the input variable exceeds the threshold value by 1.1 times, the characteristic curve is processed.
An integrating method of measurement totalizes the weighted time. The weighted time results from the char-
acteristic curve. For this, the time that is associated with the present current value is determined from the
characteristic curve. Once the weighted time exceeds the value 1, the stage operates.
When the measured value falls short of the pickup value by a factor of 1.045 (0.95 x 1.1 x threshold value),
the dropout is started. The pickup will be indicated as clearing. You can influence the dropout behavior via
setting parameters. You can select between instantaneous dropout (totalized time is deleted) or dropout
according to the characteristic curve (reduction of totalized time depending on the characteristic curve). The
dropout according to characteristic curve (disk emulation) is the same as turning back a rotor disk. The
weighted reduction of the time is initiated from 0.9 of the set threshold value.
6.6.6
6.6.6.1
Protection and Automation Functions
6.6 Directional Overcurrent Protection, Phases
428
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Содержание 7SJ82
Страница 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...