With the
Min. time of the curve
parameter, you define a minimum operate delay time. The operate
delay time of inverse-time characteristic curve never falls below the minimum operate delay time. If the
setting is left on its default value of 0 s, this parameter has no effect on the inverse-time characteristic curve.
This parameter is only required for time coordination in recloser schemes. For all other applications, Siemens
recommends keeping the default setting of 0 s.
i
i
NOTE
If the set value is smaller than the smallest possible time delay of the inverse-time characteristic curve, the
parameter has no influence on the delay time.
Parameter:
Additional time delay
•
Recommended setting value
(_:781:115) Additional time delay
=
0.00 s
With the
Additional time delay
parameter, you define a definite-time delay in addition to the inverse-
time delay.
If the setting is left on its default value of 0 s, this parameter has no effect on the inverse-time characteristic
curve.
This parameter is only required for time coordination in recloser schemes. For all other applications, Siemens
recommend keeping the default setting of 0 s.
Parameter:
Threshold
•
Default setting
(_:781:3) Threshold
=
1.20 A
The setting depends on the minimal occurring ground-fault current. This must be determined.
Parameter:
Time dial
•
Default setting
(_:781:101) Time dial
=
1
With the
Time dial
parameter, you displace the characteristic curve in the time direction.
The set value for the
Time dial
parameter is derived from the time-grading schedule that has been prepared
for the electrical power system.
Where no time grading and therefore no displacement of the characteristic curve is required, leave the
Time
dial
parameter at
1
.
Parameter:
Reset
•
Default setting
(_:781:109) Reset
=
disk emulation
With the
Reset
parameter, you define whether the stage drops out according to the dropout characteristic
curve (in accordance with the behavior of a disk emulation = rotor disk) or instantaneously.
Parameter Value
Description
disk emulation
Select this setting if the device is coordinated with electromechanical
devices or other devices which perform a dropout after a disk emulation.
instantaneous
Select this setting if the dropout is not to be performed after disk emulation
and an instantaneous dropout is desired instead.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
General
_:781:1
Inverse-T 1:Mode
•
off
•
on
•
test
off
_:781:2
Inverse-T 1:Operate &
flt.rec. blocked
•
no
•
yes
no
6.5.5.3
Protection and Automation Functions
6.5 Overcurrent Protection, Ground
394
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Содержание 7SJ82
Страница 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...