[loMasValue-201507-01.vsd, 1, en_US]
Figure 6-34
Logic Diagram of Measured-Value Selection
Both options are only available for the current-transformer connection types
3-phase + IN
and
3-phase +
IN-separate
. For other connection types respectively, only one option is possible. If you select an option
that is not allowed, an inconsistency message is given.
Depending on the CT secondary rated current, the CT connection type, and the selected setting, the secondary
threshold setting range varies according to the following table.
Table 6-2
Threshold Setting Range
Connec-
tion
Type
Measured
Value
CT
Terminal
Type
Threshold Setting
Range (rated I-sec.:
ph = 1 A, IN = 1 A)
Threshold Setting
Range (rated I-sec.:
ph = 1 A, IN = 5 A)
Threshold Setting
Range (rated I-sec.:
ph = 5 A, IN = 1 A)
Threshold Setting
Range (rated I-sec.:
ph = 5 A, IN = 5 A)
3ph + IN
3I0 calcu-
lated
4 * Protec-
tion
0.010 A to 35.000 A N/A
N/A
0.050 A to 175.00 A
4 * Meas-
urement
0.001 A to 1.600 A
N/A
N/A
0.002 A to 8.000 A
IN meas-
ured
4 * Protec-
tion
0.010 A to 35.000 A N/A
N/A
0.050 A to 175.00 A
4 * Meas-
urement
0.001 A to 1.600 A
N/A
N/A
0.002 A to 8.000 A
3ph + IN-separate
3I0 calcu-
lated
4 * Protec-
tion
0.010 A to 35.000 A 0.010 A to 35.000 A 0.050 A to 175.00 A 0.050 A to 175.00 A
3 * Protec-
tion, 1 *
sen.
0.010 A to 35.000 A 0.010 A to 35.000 A 0.050 A to 175.00 A 0.050 A to 175.00 A
4 * Meas-
urement
0.001 A to 1.600 A
0.001 A to 1.600 A
0.002 A to 8.000 A
0.002 A to 8.000 A
IN meas-
ured
4 * Protec-
tion
0.010 A to 35.000 A 0.050 A to 175.00 A 0.010 A to 35.000 A 0.050 A to 175.00 A
3 * Protec-
tion, 1 *
sen.
0.001 A to 1.600 A
0.002 A to 8.000 A
0.001 A to 1.600 A
0.002 A to 8.000 A
4 * Meas-
urement
0.001 A to 1.600 A
0.002 A to 8.000 A
0.001 A to 1.600 A
0.002 A to 8.000 A
Application and Setting Notes
Parameter:
Measured value
•
Recommended setting value
Measured value
=
IN Measured
This parameter is not available in the basic function.
Parameter Value
Description
6.5.3.2
Protection and Automation Functions
6.5 Overcurrent Protection, Ground
380
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Содержание 7SJ82
Страница 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...