Parameter:
Duration of V-seal-in time
•
Default setting
(_:104) Duration of V-seal-in time
=
4.00 s
The parameter
Duration of V-seal-in time
limits the pickup seal-in induced by an overcurrent or
undervoltage. The value must be set higher than the value of the parameter
Operate delay
. The difference
shall be greater than 0.5 s. In the default setting, a difference of 1 s is used.
Parameter:
Vph-ph< threshold
•
Default setting
(_:105) Vph-ph< threshold
=
60.000 V
With the parameter
Vph-ph< threshold
, you can set the threshold at which the output signal
Voltage
release
is activated when the minimum phase-to-phase voltage falls below this threshold.
Parameter:
V2> threshold
•
Default setting
(_:106) V2> threshold
=
4.600 V
With the parameter
V2> threshold
, you can set the threshold at which the output signal
Voltage
release
is issued when V2 exceeds the threshold.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Vseal-in+Vrel#
_:1
Vseal-in+Vrel#:Mode
•
off
•
on
•
test
off
_:2
Vseal-in+Vrel#:Operate
& flt.rec. blocked
•
no
•
yes
no
_:3
Vseal-in+Vrel#:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A
1.350 A
5 A @ 100 Irated 0.150 A to 175.000 A
6.750 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.350 A
5 A @ 50 Irated
0.150 A to 175.000 A
6.750 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.350 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
6.750 A
_:6
Vseal-in+Vrel#:Operate
delay
0.00 s to 60.00 s
3.00 s
_:10
Vseal-in+Vrel#:Blk. by
meas.-volt. failure
•
no
•
yes
yes
_:101
Vseal-in+Vrel#:State of
V-seal-in
•
off
•
on
off
_:102
Vseal-in+Vrel#:V-seal-in
threshold
0.300 V to 175.000 V
46.200 V
_:104
Vseal-in+Vrel#:Duration
of V-seal-in time
0.10 s to 60.00 s
4.00 s
_:105
Vseal-in+Vrel#:Vph-ph<
threshold
0.300 V to 175.000 V
60.000 V
_:106
Vseal-in+Vrel#:V2>
threshold
0.300 V to 200.000 V
4.600 V
6.4.6.3
Protection and Automation Functions
6.4 Voltage-Dependent Overcurrent Protection, Phases
376
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Содержание 7SJ82
Страница 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Страница 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...