MSCDN – MP2A Performance Specification
Operating Time
Characteristic Ranges
IEC
IDMTL
CURVES
Operate times are calculated from:
[ ]
⎥
⎥
⎦
⎤
⎢
⎢
⎣
⎡
−
×
=
1
α
Is
I
K
Tm
t
I = fault current
Is = current setting
Tm = time multiplier
NI: K = 0.14,
α
= 0.02
VI: K = 13.5,
α
= 1.0
EI: K = 80.0,
α
= 2.0
LTI: K = 120.0,
α
= 1.0
Time Multiplier
0.025 to 1.600
Δ
0.025 sec
Reset
0.0 to 60.0
Δ
1.0 sec
ANSI
IDMTL
CURVES
Operate times are calculated from:
[ ]
⎥
⎥
⎦
⎤
⎢
⎢
⎣
⎡
+
−
×
=
B
A
M
t
P
Is
I
1
I = fault current
Is = current setting
M = time multiplier
MI: A = 0.0515, B = 0.114, P = 0.02
VI: A = 19.61, B = 0.491, P = 2.0
EI: A = 28.2, B = 0.1217, P = 2.0
ANSI
RESET
CURVES
Operate times are calculated from:
[ ]
⎥
⎥
⎦
⎤
⎢
⎢
⎣
⎡
−
×
=
1
2
Is
I
R
M
t
I = fault current
Is = current setting
M = time multiplier
MI: R = 4.85
VI: R = 21.6
EI: R = 29.1
4.11 51N Derived Earth Fault
Inverse time derived earth fault element.
Accuracy
Pickup
105% of setting ± 5% or ± 0.02 I
n
Reset
≥
95% of I
s
Repeatability ±
2%
Operate Time
± 5% or ± 40ms
Frequency Range
1
st
, 2
nd
…15
th
Harmonic
©2011 Siemens Protection Devices Limited
Chapter 2 Page 11 of 13