MSCDN – MP2A Performance Specification
Accuracy
Pickup
100% of setting ± 5% or ± 0.02 I
n
Reset
≥
95% of I
s
Repeatability ±
2%
Operate Time
± 1% or ± 10ms
Frequency Range
1
st
, 2
nd
…15
th
Harmonic
Operating Time
Current Applied
Typical
2 x setting
2 cycles
4 x setting
1.5 cycle
4.9 50N Backup Earth Fault
Definite time derived earth fault element.
Accuracy
Pickup
100% of setting ± 5% or ± 0.02 I
n
Reset
≥
95% of I
s
Repeatability ±
2%
Operate Time
± 1% or ± 10ms
Frequency Range
1
st
, 2
nd
…15
th
Harmonic
Operating Time
Current Applied
Typical
2 x setting
2 cycles
4 x setting
1.5 cycle
4.10 51 Backup Overcurrent,
Three phase inverse time overcurrent element.
Accuracy
Pickup
105% of setting ± 5% or ± 0.02 I
n
Reset
≥
95% of I
s
Repeatability ±
2%
Operate Time
± 5% or ± 40ms
Frequency Range
1
st
, 2
nd
…15
th
Harmonic
©2011 Siemens Protection Devices Limited
Chapter 2 Page 10 of 13