7SG12 DAD N Relay Settings
©2010 Siemens Protection Devices Limited
Chapter 3 Page 17 of 20
Address Description
10128
CT Supervision Phase C
4.3 Registers
Address Description
Format
30001
No. of Events In Store (See 434/TIR/15)
1 Register
30002
Latest Event Record (See 434/TIR/15)
8 Registers
Address Description
Format
30010
Ia Primary
FP_32BITS_3DP
1
30012
Ib Primary
FP_32BITS_3DP
1
30014
Ic Primary
FP_32BITS_3DP
1
30016
Ia Secondary
FP_32BITS_3DP
1
30018
Ib Secondary
FP_32BITS_3DP
1
30020
Ic Secondary
FP_32BITS_3DP
1
30022
Ia Nominal
FP_32BITS_3DP
1
30024
Ib Nominal
FP_32BITS_3DP
1
30026
Ic Nominal
FP_32BITS_3DP
1
30028 Fault
Records
UINT16
2
30029 Event
Records
UINT16
2
30030 Waveform
Records
UINT16
2
1) FP_32BITS_3DP: 2 registers - 32 bit fixed point, a 32 bit integer containing a value to 3 decimal places e.g. 50000 sent = 50.000
2) UINT16: 1 register - standard 16 bit unsigned integer
5 Reylogic Diagrams
General Trip
General_Trip
PhaseA_Trip
PhaseB_Trip
PhaseC_Trip
PhaseA_Starter
CT_50_Starter1
A87_50_1_Starter1
PhaseB_Starter
PhaseC_Starter
IEC Event Code 181-64
IEC Event Code 181-65
IEC Event Code 181-66
IEC Event Code 181-84
IEC Event Code 181-69
IEC Event Code 181-70
IEC Event Code 181-71
IEC Event Code 181-68
General Starter
General_Starter
STARTER LOGIC (Includes CT elements)
A87_50_1_Operated1
A87_50_1_Operated2
A87_50_1_Operated3
CT_50_Starter2
A87_50_1_Starter2
CT_50_Starter3
A87_50_1_Starter3
1
PhaseA_Starter
PhaseB_Starter
PhaseC_Starter
1
PhaseA_Trip
PhaseB_Trip
PhaseC_Trip
IntTriggerData
IntTriggerWavef orm
1
A87_50_2_Starter1
1
A87_50_2_Starter2
1
A87_50_2_Starter3
1
A87_50_2_Operated1
A87_50_2_Operated2
1
1
A87_50_2_Operated3
GENERAL TRIP LOGIC
Содержание 7SG12 DAD-N
Страница 2: ......