Parameter assignment
7.3 P003 Measurement response
SITRANS Probe LR with mA/HART
Operating Instructions, 05/2019, A5E32337711-AC
43
①
Reference point
④
Empty
②
Span
⑤
Space
③
Level
⑥
Distance
Note
•
Setting P001 resets Span (P007), unless Span has previously been set to a different
value. Span is set to Empty distance minus 110% of Blanking unless P001 is set to 3
(distance measurement). In that case it is set to the same value as Empty (P006). See
Near blanking (Page 87)
for more details.
•
Changing P001 may reset Output Function (P201). This applies to HART only.
7.3
P003 Measurement response
Sets the rate of response to level changes.
Related
parameters
P003
Failsafe
Timer P070
(minutes)
Max. measure-
ment response
P700/P701
Damping filter
Echo verification
Values
1 * slow
100
0.1 m/minute
10.0 s
2
2 medium 10
1 m/minute
10.0 s
2
3 fast
1
10 m/minute
1.0 s
2
Note
Changing P003 resets the following parameters: P070, P700, P701, P709, and P711.