Pulse width (menu 4.2.4)
This parameter is only required for the "Pulse" output function. You can set the pulse/pause ratio
of the pulse output with the pulse width. The pulse width can be set in a range from 0.1 to 2000
ms. A maximum pulse width is calculated in relation to the set full scale value and the set pulse
valence. The maximum pulse frequency is 5 kHz.
Full scale frq (menu 4.2.5)
The frequency is permanently assigned to the flow. The pulse/pause ratio is constant 1:1. If the
"Frequency" function is selected, the "Full scale frq" is set in the range from 2 to 10 000 Hz.
7.5
Identification (menu 5)
In this menu the device-specific data can be entered or read.
Unit identity (menu 5.1)
You can call or enter device-specific or TAG-related data in this menu.
You have the following options:
• TAG number, menu 5.1.1 (max. 8 characters)
• TAG description, menu 5.1.2 (max. 32 characters)
• TAG message, menu 5.1.3 (max. 32 characters)
TAG-specific data can be entered in these menus. The and keys function as cursor control.
Numbers, letters and text characters are selected with the and keys.
If no text is stored, a "<" is displayed. By actuating the and keys, the "<" moves one position
to the right and a character can be selected from the character set. The following characters are
available:
Output
position
ä,à...é...ß...ü a-z blank 0-9 A-Z < >.,-:/*
<
>
<
>
>
Output
position
ä,à...é...ß...ü a-z blank 0-9 A-Z < >.,-:/*
<
>
<
>
>
The selected character is entered by actuating the key and the "<" flashes again. The next
character can then be selected with the and keys. The text input is finalized by actuating
the key when the "<" flashes.
For texts longer than 16 characters the marks < and > in the most left and/or the most right
position of the display indicate that there are further characters to the left and/or right of the
displayed text section. These are displayed by actuating the and keys.
Functions
7.5 Identification (menu 5)
SITRANS FUS060 with PROFIBUS PA
Operating Instructions, 09/2021, A5E02225054-AD
63