Conformity with European directives
The CE marking on the device symbolizes the conformity with the following European directives:
Electromagnetic compatibil‐
ity EMC
2014/30/EU
Directive of the European Parliament and of the Council on the
harmonisation of the laws of the Member States relating to elec‐
tromagnetic compatibility
Low voltage directive LVD
2014/35/EU
Directive of the European Parliament and of the Council on the
harmonisation of the laws of the Member States relating to the
making available on the market of electrical equipment designed
for use within certain voltage limits
Atmosphère explosible ATEX
2014/34/EU
Directive of the European Parliament and the Council on the har‐
monisation of the laws of the Member States relating to equip‐
ment and protective systems intended for use in potentially ex‐
plosive atmospheres
Pressure equipment direc‐
tive PED
2014/68/EU
Directive of the European Parliament and of the Council on the
harmonisation of the laws of the Member States relating to the
making available on the market of pressure equipment
2011/65/EU RoHS
Directive of the European Parliament and the Council on the re‐
striction of the use of certain hazardous substances in electrical
and electronic equipment
The applicable directives can be found in the EU declaration of conformity of the specific device.
Further country or region-specific code conformity information is available on request.
2.3
Installation in hazardous area
WARNING
Equipment used in hazardous locations
Equipment used in hazardous locations must be Ex-approved for the region of installation and
marked accordingly. It is required that the special conditions for safe use provided in the
manual and in the Ex certificate are followed!
WARNING
500 V insulation test
The device is not capable of withstanding the 500 V insulation test required by Clause 6.3.12
of EN60079-11. This must be taken into account when installing the device.
Hazardous area approvals
The device is approved for use in hazardous area and has the following approval:
• PTB 07 ATEX 2033 X with the marking: II 2 G Ex db eb mb [ia Ga] IIC T6…T3 Gb
The device's compliance with Essential Health and Safety Requirements has been assured by
compliance with:
Safety notes
2.3 Installation in hazardous area
SITRANS FUS060 with PROFIBUS PA
12