Interaction with Control and External Triggering
With Control
The control and synchronization function are always located in a function group Circuit breaker. The control
and also the synchronization function always operate with the circuit breaker, which is linked to the function
group Circuit breaker.
As soon as the synchronization function is in the function group Circuit breaker, the circuit breaker is subject
to compulsory synchronization. If all synchronization stages are deactivated, the circuit breaker cannot be acti-
vated via the control, as no release can be generated for the closure. The circuit breaker is no longer subject to
compulsory synchronization after deletion of the synchronization function. Closure without synchronization is
then possible via the control.
If closure is to be synchronized via the control, the control automatically generates an internal signal which
starts the synchronization function. The functional sequence is described in chapter
closes the circuit breaker and then stops and synchronization function.
[losynaw1-310111-01.tif, 1, en_US]
Figure 6-93
Interaction of the Control with the Synchronization Function
With External Control
You have the option of controlling the synchronization function externally via binary input signals. This can be
done as follows:
•
Edge-controlled
•
Via the signals
>Start syn. process
and
>Stop syn. process
•
State-controlled, via the signal
>Start / stop syn.proc.
(see also chapter
).
The start is followed by the functional sequence (see chapter
). If the conditions
are fulfilled, the output signal
Release close cmd.
is issued. The switched object QAx of the function
group Circuit breaker is not closed. The output signal
Release close cmd.
must be explicitly assigned to
the binary output in order to close the circuit breaker.
6.4.13
Control Functions
6.4 Synchronization Function
SIPROTEC 5, High-Voltage Bay Controller, Manual
413
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...