Addr.
Parameter
C
Setting Options
Default Setting
_:124
Syn./Asy.bal.#:Max.
angle diff. α2>α1
0 ° to 90 °
10 °
_:125
Syn./Asy.bal.#:Max.
angle diff. α2<α1
0 ° to 90 °
10 °
_:121
Syn./Asy.bal.#:Delay
close command
0.00 s to 60.00 s
0.00 s
Balancing V
_:131
Syn./Asy.bal.#:Balancing
voltage V2
•
off
•
transformer tap
•
balancing pulses
off
_:132
Syn./Asy.bal.#:T V pulse
min
0.01 s to 1.00 s
0.10 s
_:133
Syn./Asy.bal.#:T V pulse
max
0.01 s to 60.00 s
1.00 s
_:134
Syn./Asy.bal.#:dV per
second
0.100 V/s to 50.000 V/s
2.000 V/s
_:135
Syn./Asy.bal.#:T pause V
0.10 s to 60.00 s
5.00 s
_:136
Syn./
Asy.bal.#:Smoothing
1 to 100
1
_:137
Syn./Asy.bal.#:(V/
Vrated)/(f/frated)
1.00 to 1.40
1.10
Balancing f
_:141
Syn./Asy.bal.#:Balancing
frequency f2
•
off
•
balancing pulses
off
_:142
Syn./Asy.bal.#:T f pulse
min
0.01 s to 1.00 s
0.10 s
_:143
Syn./Asy.bal.#:T f pulse
max
0.01 s to 60.00 s
1.00 s
_:144
Syn./Asy.bal.#:df/dt of
the controller
0.05 Hz/s to 5.00 Hz/s
1.00 Hz/s
_:145
Syn./Asy.bal.#:T pause f
0.10 s to 60.00 s
10.00 s
_:146
Syn./Asy.bal.#:Δf set
point for balancing
-1.00 Hz to 1.00 Hz
0.04 Hz
_:147
Syn./
Asy.bal.#:Smoothing
1 to 100
1
_:148
Syn./Asy.bal.#:T close
without balancing
1.00 s to 100.00 s
5.00 s
_:149
Syn./Asy.bal.#:Release
for the kick pulse
•
off
•
on
off
_:150
Syn./Asy.bal.#:Δf for the
kick pulse
-1.00 Hz to 1.00 Hz
0.04 Hz
_:151
Syn./Asy.bal.#:Stabiliza-
tion
•
no
•
yes
no
Information List
No.
Information
Data Class
(Type)
Type
Syn./Asy.bal.#
_:81
Syn./Asy.bal.#:>Block stage
SPS
I
_:500
Syn./Asy.bal.#:>Selection
SPS
I
6.4.9.4
Control Functions
6.4 Synchronization Function
406
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...