Redundant PROFIBUS DP interface
32
SIPROTEC PROFIBUS DP - Bus mapping 6MD662/3/4
C53000-L1840-B011-03
After redundancy start-up:
•
Time until the next Check.req telegram is sent for supervision of the RedCom com-
munication and the partner module .
The reload value for the timer of Check.req. telegrams is 5 seconds (not change-
able).
This module information line shows:
•
the current timer value,
•
an expiring counter,
•
an indication whether the timer is currently running (N = not running, R = running).
Unlike RedTrc (see above), the expiring counter in the RedTsp line should be incre-
mented cyclically. This shows that the next action (e.g. switchover to S_BACKUP or
sending of a Check.req telegram) is executed.
Ttoggl
Supervision time of the Toggle bit mechanism.
Every changeover of the Toggle bits in the output telegram to a valid bit combination
re-triggers the Toggle bit timer.
This module information line shows:
•
the current timer value,
•
an expiring counter,
•
an indication whether the timer (i.e. the Toggle bit mechanism) is currently running
(N = not running, R = running).
Please ref. to chap. 1.4.1.4 for a description of the Toggle bit mechanism.
If the Toggle bit mechanism is deactivated, then this is shown in this line as:
Ttoggl: OFF
Содержание 6MD662
Страница 6: ...Preview 6 SIPROTEC PROFIBUS DP Bus mapping 6MD662 3 4 C53000 L1840 B011 03 ...
Страница 8: ...Revision index 8 SIPROTEC PROFIBUS DP Bus mapping 6MD662 3 4 C53000 L1840 B011 03 ...
Страница 12: ...Table of contents 12 SIPROTEC PROFIBUS DP Bus mapping 6MD662 3 4 C53000 L1840 B011 03 ...
Страница 72: ...Standard mapping 3 2 72 SIPROTEC PROFIBUS DP Bus mapping 6MD662 3 4 C53000 L1840 B011 03 ...
Страница 86: ...Index 86 SIPROTEC PROFIBUS DP Bus mapping 6MD662 3 4 C53000 L1840 B011 03 ...