Diagnostics and error messages
7.4 Parameterization of the diagnostics
SIMATIC RF170C
48
Operating Instructions, 02/2022, J31069-D0176-U001-A6-7618
I&M data
Access
Default
Explanation
Maintenance data 1: Index 2 (data record 232 or =0xAFF1)
TAG_FUNCTION
read / write (32
bytes)
-
Here, enter an ID for the module here that
is unique in the entire plant.
TAG_LOCATION
read / write (22
bytes)
-
Here enter the installation location of the
module.
Maintenance data 2: Index 3 (data record 233 or =0xAFF2)
INSTALLATION_DATE
read / write (16
bytes)
-
Here, enter the installation date of the
module.
RESERVED
read / write (38
bytes)
-
Reserved
Maintenance data 3: Index 4 (data record 234 or =0xAFF3)
DESCRIPTOR
read / write (54
bytes)
-
Here, enter a comment describing the
module.
7.4
Parameterization of the diagnostics
In addition to the PROFIBUS / PROFINET standard diagnostics, the RF170C offers user-specific
diagnostics data integrated in the diagnostics of the interface module.
The diagnostics data can be read out as follows:
•
as plain text in the STEP 7 user interface
•
on PROFIBUS DP
–
Read out with SFC 13 slave diagnostics and store in the data area of the application
•
on PROFINET IO
–
Read data records from the IO device with SFB 52
–
Receive alarms from the IO device with SFB 54
•
Evaluation with FB 125 or FC 125
Parameter assignment options
•
None
No other diagnostics data is reported, apart from standard diagnostics.
•
Hard errors
Extended diagnostics messages are generated in the case of the following events.
–
Hardware fault (memory test)
–
Firmware error (checksum)
–
Connection to reader lost
–
Short-circuit fault/interruption, if supported by hardware
–
Firmware update (message at start/end)
In the case of this diagnostics, the “Ext_Diag” bit is set, that is, it is treated as high-priority
diagnostics information in the controller (SF-LED is lit)